Summary for Test 2014-09-04-5-1

Test performed: ASTM C39-10

Project Information

Project IdentifiersProject ID: 209114
DEA: 040A7104
EFIS: 0400000160
COOP: 042550
DIST-CO-RTE-PM04-ALA-880-28.4/29.2
Award Date04/30/2014
Closeout Date07/23/2020
Work DescriptionWIDEN ROADS, RECONSTRUCT RAMPS WITH HMA, REPLACE 2 CONC OVERCROSSINGS.
Location DescriptionALAMEDA COUNTY IN ALAMEDA AND OAKLAND FROM 0.2 MILE SOUTH OF 29TH AVENUE OVERCROSSING TO 0.3 MILE NORTH OF 23RD AVENUE OVERCROSSING.
QA Service Level1 (Verified on 10/11/2013)

Sample Information

Sample Taken Date09/04/2014 Sample Unique Key5
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing09/05/2014
Sample typeQuality Control A brief description of the sampleconcrete cylinder
The quantity of what the sample constitutes4 concrete cylinder From where was the sample collectedOther
First name of sampler or witnessed byna Last name of sampler or witnessed byna
Title of sampler Telephone number of sampler
Laboratory sample identificationcl141060 Linked DIME Sample IDNot set
The fabricator/manufacturer/facility namefield Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name

Material Information

Material TypeConcrete The concrete mix design numberna
The truck number from where the sample was collected The batch plant ticket number from where the sample was collectedn
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedfield Where the material sample would have been placed if not sampledNot set
From Lot No.Not set Bag Lot No.Not set

Test Details

DIME Sample ID: 2014-09-04-5
DIME Test ID: 2014-09-04-5-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2014-09-11

Test Results


Unit system used?: US Units
Number of specimens: 4
Test performed: With no density determined
Input Type: Measured
Tester's full name: mullins
Date of test: 09/11/2014
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.02 in
Average diameter of cylinder 2: 6.02 in
Average diameter of cylinder 3: 6.03 in
Average diameter of cylinder 4: 6.02 in
Maximum load on cylinder 1: 112925 lb
Maximum load on cylinder 2: 114531 lb
Maximum load on cylinder 3: 110224 lb
Maximum load on cylinder 4: 109163 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Type of fracture pattern of cylinder 3: 1
Type of fracture pattern of cylinder 4: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: no data
Correction factor for cylinder 3: no data
Correction factor for cylinder 4: no data
Age of specimen: 7 days
Cross sectional area of cylinder 1: 28.46 in^2
Cross sectional area of cylinder 2: 28.46 in^2
Cross sectional area of cylinder 3: 28.56 in^2
Cross sectional area of cylinder 4: 28.46 in^2
Compressive strength of cylinder 1: 3967.8 psi
Compressive strength of cylinder 2: 4024.3 psi
Compressive strength of cylinder 3: 3859.4 psi
Compressive strength of cylinder 4: 3835.7 psi
Compressive strength (to nearest 10 psi): 3920 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 9/11/2014