Summary for Test 2019-08-02-8-1

Test performed: ASTM C39-10

Project Information

Project IdentifiersProject ID: 210837
DEA: 080J0804
EFIS: 0800000283
COOP: 081625
DIST-CO-RTE-PM08-RIV-15-34.7/51.6
Award Date04/17/2017
Closeout DateNot set
Work Description(Alternative Delivery) DESIGN-BUILD OF THE INTERSTATE 15 EXPRESS LANES PROJECT
Location DescriptionRiverside County and SBD-15-0.0/1.3
QA Service Level1 (Verified on 05/08/2017)

Sample Information

Sample Taken Date08/02/2019 Sample Unique Key8
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing08/05/2019
Sample typeQuality Assurance A brief description of the sample6x12 concrete cylinders
The quantity of what the sample constitutes4 From where was the sample collectedJob Site
First name of sampler or witnessed bySAYED Last name of sampler or witnessed byMIRGATI
Title of samplerTET Telephone number of sampler
Laboratory sample identification974-86 Linked DIME Sample ID
The fabricator/manufacturer/facility nameROBERTSON REDLAND Transportation Laboratory (TL) Number86
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure nameLIGHT POLE STA 2460 45

Material Information

Material TypeConcrete The concrete mix design numberSM446B38
The truck number from where the sample was collected1736 The batch plant ticket number from where the sample was collected4808043
Concrete batch plantUnknown The fabricator/manufacturer designation for the sampleSKANSKA AMES
A detailed description of where the material sample was collected8 CY Where the material sample would have been placed if not sampledLIGHT POLE STA 2460 45
From Lot No.Unknown Bag Lot No.Unknown

Test Details

DIME Sample ID: 2019-08-02-8
DIME Test ID: 2019-08-02-8-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2019-09-04

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: MM
Date of test: 08/30/2019
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.03 in
Average diameter of cylinder 2: 6.03 in
Maximum load on cylinder 1: 148620 lb
Maximum load on cylinder 2: 148960 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 28 days
Cross sectional area of cylinder 1: 28.56 in^2
Cross sectional area of cylinder 2: 28.56 in^2
Compressive strength of cylinder 1: 5203.8 psi
Compressive strength of cylinder 2: 5215.7 psi
Compressive strength (to nearest 10 psi): 5210 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 9/4/2019