Test 2014-06-04-8419685-3 (ASTM C39-10) Summary

Project Information
Project IdentifiersProject ID: 209175
DEA: 030F2204
EFIS: 0300000072
DIST-CO-RTE-PM03-ED-50-R30.7/R31.7
Work DescriptionREPLACE BRIDGE.
Location DescriptionSLY PARK UNDERCROSSING
Sample Information
Sample Taken Date6/4/2014 Sample Unique Key8419685
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testingNot set
Sample typeVerification A brief description of the sampleConcrete in a wheelbarrow
The quantity of what the sample constitutes.1 cy in a wheelbarrow From where was the sample collectedOther
First name of sampler or witnessed byBrandon Last name of sampler or witnessed byMiller
Title of samplerSR Laboratory sample identificationNot set
The fabricator/manufacturer/facility nameJobsite Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier25-0042
Structure nameSly Park Rd UC
Material Information
Material TypeConcrete The concrete mix design numberSF718AFST0
The truck number from where the sample was collected32 The batch plant ticket number from where the sample was collected1043969
Concrete batch plant1B The fabricator/manufacturer designation for the sampleNot set
A detailed description of where the material sample was collectedDischarge from concrete truck into wheelbarrow. Where the material sample would have been placed if not sampledStage 1 Abutment 1
From Lot No.Not set Bag Lot No.Not set
Test Details
DIME Sample ID: 2014-06-04-8419685
DIME Test ID: 2014-06-04-8419685-3
Testing Lab: CT D03 - Sacramento Structures Construction Sanders Construction Field Laboratory Office
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2014-07-23
Test Results

Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Bang Nguyen
Date of test: 07/02/2014
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.02 in
Average diameter of cylinder 2: 6.03 in
Maximum load on cylinder 1: 142714 lb
Maximum load on cylinder 2: 139851 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: no data
Age of specimen: 28 days
Cross sectional area of cylinder 1: 28.46 in^2
Cross sectional area of cylinder 2: 28.56 in^2
Compressive strength of cylinder 1: 5014.5 psi
Compressive strength of cylinder 2: 4896.7 psi
Compressive strength (to nearest 10 psi):4960 psi
General comments (publicly viewable) (Max 250 characters):

Test was verified on 07/23/2014