Summary for Test 2018-09-17-10-2

Test performed: ASTM C39-10

Project Information

Project IdentifiersProject ID: 210837
DEA: 080J0804
EFIS: 0800000283
COOP: 081625
DIST-CO-RTE-PM08-RIV-15-34.7/51.6
Award Date04/17/2017
Closeout DateNot set
Work Description(Alternative Delivery) DESIGN-BUILD OF THE INTERSTATE 15 EXPRESS LANES PROJECT
Location DescriptionRiverside County and SBD-15-0.0/1.3
QA Service Level1 (Verified on 05/08/2017)

Sample Information

Sample Taken Date09/17/2018 Sample Unique Key10
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing09/20/2018
Sample typeQuality Assurance A brief description of the sample6x12 concrete cylinders
The quantity of what the sample constitutes8 From where was the sample collectedJob Site
First name of sampler or witnessed byJose Last name of sampler or witnessed byDiaz
Title of samplerTET Telephone number of samplerUnknown
Laboratory sample identification974-1 Linked DIME Sample IDUnknown
The fabricator/manufacturer/facility namerobertson Transportation Laboratory (TL) Number1
Inspector Lot Number from the Transportation Laboratory (TL) FormUnknown Structure unique identifierN I15 ONTARIO ON RAMP
Structure nameN I15 ONTARIO ON RAMP

Material Information

Material TypeConcrete The concrete mix design numberrrm18109
The truck number from where the sample was collected1132 The batch plant ticket number from where the sample was collected3919960
Concrete batch plantUnknown The fabricator/manufacturer designation for the sampleSKANSKA AMES
A detailed description of where the material sample was collectedat 5 yards Where the material sample would have been placed if not sampledN I15 ONTARIO ON RAMP
From Lot No.Unknown Bag Lot No.Unknown

Test Details

DIME Sample ID: 2018-09-17-10
DIME Test ID: 2018-09-17-10-2
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2018-10-10

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: MC
Date of test: 10/01/2018
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.00 in
Average diameter of cylinder 2: 6.00 in
Maximum load on cylinder 1: 88630 lb
Maximum load on cylinder 2: 90510 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 14 days
Cross sectional area of cylinder 1: 28.27 in^2
Cross sectional area of cylinder 2: 28.27 in^2
Compressive strength of cylinder 1: 3135.1 psi
Compressive strength of cylinder 2: 3201.6 psi
Compressive strength (to nearest 10 psi): 3170 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 10/3/2018