Summary for Test 2018-06-14-7-1

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 210837
DEA: 080J0804
EFIS: 0800000283
COOP: 081625
DIST-CO-RTE-PM08-RIV-15-34.7/51.6
Award Date04/17/2017
Closeout DateNot set
Work Description(Alternative Delivery) DESIGN-BUILD OF THE INTERSTATE 15 EXPRESS LANES PROJECT
Location DescriptionRiverside County and SBD-15-0.0/1.3
QA Service Level1 (Verified on 05/08/2017)

Sample Information

Sample Taken Date06/14/2018 Sample Unique Key7
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing06/19/2018
Sample typeQuality Assurance A brief description of the sample6x12 concrete cylinders
The quantity of what the sample constitutes4 From where was the sample collectedFabricator
First name of sampler or witnessed byrobertsons Last name of sampler or witnessed byroy fisher
Title of samplerINDEPENDENT QA Telephone number of samplerUnknown
Laboratory sample identification974-614B Linked DIME Sample IDUnknown
The fabricator/manufacturer/facility nameRobertsons Redlands Transportation Laboratory (TL) Number974-614B
Inspector Lot Number from the Transportation Laboratory (TL) FormUnknown Structure unique identifierdesign build for I15 express lanes project
Structure namedesign build for I15 express lanes project

Material Information

Material TypeConcrete The concrete mix design numberSC270N31
The truck number from where the sample was collectedna The batch plant ticket number from where the sample was collectedna
Concrete batch plantrobertsons The fabricator/manufacturer designation for the sampleAMES CONSTRUCTION
A detailed description of where the material sample was collectedBatch plant Where the material sample would have been placed if not sampleddesign build for I15 express lanes project
From Lot No.Unknown Bag Lot No.Unknown

Test Details

DIME Sample ID: 2018-06-14-7
DIME Test ID: 2018-06-14-7-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2018-06-29

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: MM
Date of test: 06/21/2018
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.01 in
Average diameter of cylinder 2: 6.01 in
Maximum load on cylinder 1: 22720 lb
Maximum load on cylinder 2: 21430 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 7 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.37 in^2
Cross sectional area of cylinder 2: 28.37 in^2
Compressive strength of cylinder 1: 800.8 psi
Compressive strength of cylinder 2: 755.4 psi
Compressive strength (to nearest 10 psi): 780 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 6/22/2018