Summary for Test 2016-01-21-6-1

Test performed: CTM 521-November 2014

Project Information

Project IdentifiersProject ID: 208682
DEA: 083401U4
EFIS: 0800000609
DIST-CO-RTE-PM08-SBD-138,138-6.2/6.4,2.3/R15.2
Award Date09/10/2014
Closeout Date06/23/2021
Work DescriptionWIDEN TO 4 LNS FR BEEKLEY RD TO JCT 15, ADD 1 LN EB FR PHELAN RD TO
Location DescriptionSAN BERNARDINO COUNTY ON ROUTE 138 NEAR PHELAN FROM 0.6 MILE WEST OF PHELAN ROAD TO THE JUNCTION OF ROUTE 15 AND ON ROUTE 2 FROM 0.1 MILE NORTH OF WILD HORSE CANYON ROAD TO ROUTE 138
QA Service Level1 (Verified on 03/11/2013)

Sample Information

Sample Taken Date01/21/2016 Sample Unique Key6
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing01/25/2016
Sample typeAcceptance A brief description of the sample6x12 concrete cylinders
The quantity of what the sample constitutes2 From where was the sample collectedJob Site
First name of sampler or witnessed byM Last name of sampler or witnessed byRAHMAN
Title of samplerTE Telephone number of samplerUnknown
Laboratory sample identificationUnknown Linked DIME Sample IDUnknown
The fabricator/manufacturer/facility namejob site Transportation Laboratory (TL) Number06
Inspector Lot Number from the Transportation Laboratory (TL) Form06 Structure unique identifierUnknown
Structure nameUnknown

Material Information

Material TypeConcrete The concrete mix design numberSITI72A
The truck number from where the sample was collected1 The batch plant ticket number from where the sample was collected2
Concrete batch plantUnknown The fabricator/manufacturer designation for the sampleUnknown
A detailed description of where the material sample was collectedPier wall Where the material sample would have been placed if not sampledUnknown
From Lot No.Unknown Bag Lot No.Unknown

Test Details

DIME Sample ID: 2016-01-21-6
DIME Test ID: 2016-01-21-6-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: CTM 521-November 2014: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2016-02-18

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Matthew Clayton
Date of test: 02/18/2016
Average diameter of cylinder 1: 5.98 in
Average diameter of cylinder 2: 5.98 in
Maximum load on cylinder 1: 150920 lb
Maximum load on cylinder 2: 149600 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Age of specimen: 28 days
Cross sectional area of cylinder 1: 28.09 in^2
Cross sectional area of cylinder 2: 28.09 in^2
Compressive strength of cylinder 1: 5372.7 psi
Compressive strength of cylinder 2: 5325.7 psi
Compressive strength (to nearest 10 psi): 5350 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 2/18/2016