Summary for Test 2021-09-07-11-1

Test performed: CTM 670-December 2013

Project Information

Project IdentifiersProject ID: 212252
DEA: 033F5604
EFIS: 0313000033
DIST-CO-RTE-PM03-SUT,YUB-20-17.0/17.1,0.0/0.4
Award Date02/11/2021
Closeout Date01/25/2023
Work DescriptionINSTALL CAST-IN-STEEL SHELL CONCRETE PILE.
Location DescriptionSUTTER AND YUBA COUNTIES IN YUBA CITY AND MARYSVILLE AT THE FEATHER RIVER BRIDGE AND OVERHEAD
QA Service Level1 (Verified on 04/27/2018)

Sample Information

Sample Taken Date09/07/2021 Sample Unique Key11
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing09/08/2021
Sample typeQuality Assurance A brief description of the sampleZap Screwlock Type 2 Couplers
The quantity of what the sample constitutes150 Couplers From where was the sample collectedJob Site
First name of sampler or witnessed byArya Last name of sampler or witnessed byAlishahi
Title of samplerASR Telephone number of sampler
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameC and N Reinforcing Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name

Material Information

Material TypeSMTL TM5 - Couplers Production or Authorization TestingProduction Testing
Service or UltimateService Material Standard CodeASTM A706
Material Grade60 Rebar ManufacturerNucor
Coupler ManufacturerBarSplice Intermediate Assembler or Fabricator
Rebar Size#10 Coupler ModelZap Screwlok Type 2
Coating StandardsUncoated Shape of RebarStraight
Rebar Hoop Diameter Rebar Hoop Fabricator
Coupler Component Heat/Lot Number(s)MM20104040 Rebar Heat Number(s)3500018016
Rebar Size 2 Coupler Unique IDNot set

Test Details

DIME Sample ID: 2021-09-07-11
DIME Test ID: 2021-09-07-11-1
Testing Lab: CT HQ - Sacramento Structural Materials Testing Laboratory
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Test Release Date: 2021-09-09

Test Results


Number of Samples Tested: 1
Input Type: Measured
Tester's full name: fsaylor
Date of test: 09/09/2021
UTM: 400kip
Temperature: 72.00 f
Halo ID: Large
NumSampleNumber of CyclesSizeMfg. Lot Number(s)Slip (inch)Area (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
11No. 10/32mm1-0.00561.2711810092992Service Splicefsaylor

General comments (publicly viewable) (Max 1000 characters): Service Splice
Test Graph
Source: Bluehill Data Point File
WARNING: position or load not found in data points imported from Instron machine.

Test was verified on 9/9/2021