Summary for Test 2021-07-22-36-1
Test performed: CONCLP 4-16Project Information
Project Identifiers | Project ID: 215411 DEA: 060X1904 EFIS: 0618000230 |
---|---|
DIST-CO-RTE-PM | 06-FRE,KIN-5,41,168,180,198-Var |
Award Date | 03/15/2021 |
Closeout Date | 10/04/2022 |
Work Description | PLACE POLYESTER CONCRETE OVERLAY, REPLACE JOINT SEALS AND TREAT DECK. |
Location Description | FRESNO AND KINGS COUNTIES AT VARIOUS LOCATIONS |
QA Service Level | 1 (Verified on 01/25/2021) |
Sample Information
Sample Taken Date | 07/22/2021 | Sample Unique Key | 36 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 07/22/2021 |
Sample type | Quality Assurance | A brief description of the sample | 1 gallon can |
The quantity of what the sample constitutes | 1 gallon can | From where was the sample collected | Other |
First name of sampler or witnessed by | Myers | Last name of sampler or witnessed by | Myers |
Title of sampler | Telephone number of sampler | ||
Laboratory sample identification | Linked DIME Sample ID | ||
The fabricator/manufacturer/facility name | Myers and Sons | Transportation Laboratory (TL) Number | |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name |
Material Information
Material Type | Methacrylate | Mfg. Lot Number(s) | 20-40-390489 |
---|---|---|---|
Batch number | 2040390489 | Mix number | 3532 |
Test Details
DIME Sample ID: 2021-07-22-36
DIME Test ID: 2021-07-22-36-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: CONCLP 4-16: HMWM
Test Release Date: 2021-08-04
Test Results
Input Type: Calculated
Tester's full name: Spencer Adams
Date of test: 08/04/2021
Viscosity (ASTM D 2196) Brookfield RVT with UL adapter, 50 RPM @ 77 deg F, 25 max cps @ 77 deg F: 21.76
Specific gravity (ASTM D 1475) 0.90 min @ 77 deg F: 0.91
Volatile content (ASTM D 2369) 30% max: 18.28
Flash point (ASTM D 3828) more than 180 deg F: 220
PCC - SSD bond strength (CA Test 551) 500 psi minimum @ 24 hours: no data
Tack free time, 400 minutes max: 210
General comments (publicly viewable) (Max 1000 characters): Accepted tack free time based on suppliers results. PCC Bond Strength not performed due to material being tested for recertification.
Test was verified on 8/4/2021 ✔