Summary for Test 2021-01-09-3-2

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 213746
DEA: 080Q75U4
EFIS: 0817000114
DIST-CO-RTE-PM08-SBD,RIV-60-R4.6/R9.9, R0.0/12.2
Award Date04/18/2019
Closeout Date06/28/2022
Work DescriptionREPLACEMENT OF TWO OUTSIDE LANES AND CONCRETE SLABS
Location DescriptionNot set
QA Service Level1 (Verified on 06/17/2019)

Sample Information

Sample Taken Date01/09/2021 Sample Unique Key3
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing01/20/2021
Sample typeQuality Assurance A brief description of the sampleCONCRETE CYLINDERS
The quantity of what the sample constitutesCONCRETE CYLINDERS From where was the sample collectedJob Site
First name of sampler or witnessed byPaul Last name of sampler or witnessed byPastora
Title of samplerRMA Telephone number of sampler
Laboratory sample identification999-109A Linked DIME Sample ID
The fabricator/manufacturer/facility nameShort Load Concrete Inc Transportation Laboratory (TL) Number999-109A
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name

Material Information

Material TypeConcrete The concrete mix design numberCTS-30-RAM
The truck number from where the sample was collectedNA The batch plant ticket number from where the sample was collected8
Concrete batch plantVOLUMETRIC TRUCK The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedSITE Where the material sample would have been placed if not sampledsta 46000 60 fwy EB Haven Offramp
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2021-01-09-3
DIME Test ID: 2021-01-09-3-2
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2021-03-04

Test Results


Unit system used?: US Units
Number of specimens: 6
Test performed: With no density determined
Input Type: Measured
Tester's full name: Jose Guzman
Date of test: 01/20/2021
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 5.99 in
Average diameter of cylinder 2: 6.00 in
Average diameter of cylinder 3: 6.00 in
Average diameter of cylinder 4: 6.01 in
Average diameter of cylinder 5: 6.01 in
Average diameter of cylinder 6: 6.01 in
Maximum load on cylinder 1: 34600 lb
Maximum load on cylinder 2: 33970 lb
Maximum load on cylinder 3: 34820 lb
Maximum load on cylinder 4: 33990 lb
Maximum load on cylinder 5: 34360 lb
Maximum load on cylinder 6: 34380 lb
Type of fracture pattern of cylinder 1: 4
Type of fracture pattern of cylinder 2: 4
Type of fracture pattern of cylinder 3: 2
Type of fracture pattern of cylinder 4: 2
Type of fracture pattern of cylinder 5: 4
Type of fracture pattern of cylinder 6: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Correction factor for cylinder 3: 1
Correction factor for cylinder 4: 1
Correction factor for cylinder 5: 1
Correction factor for cylinder 6: 1
Age of specimen: 11 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.18 in^2
Cross sectional area of cylinder 2: 28.27 in^2
Cross sectional area of cylinder 3: 28.27 in^2
Cross sectional area of cylinder 4: 28.37 in^2
Cross sectional area of cylinder 5: 28.37 in^2
Cross sectional area of cylinder 6: 28.37 in^2
Compressive strength of cylinder 1: 1227.8 psi
Compressive strength of cylinder 2: 1201.6 psi
Compressive strength of cylinder 3: 1231.7 psi
Compressive strength of cylinder 4: 1198.1 psi
Compressive strength of cylinder 5: 1211.1 psi
Compressive strength of cylinder 6: 1211.8 psi
Compressive strength (to nearest 10 psi): 1210 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 3/4/2021