Project Information

Project ID: 215129 DEA: 050N73U4 EFIS: 0520000166 QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-101-7.3/9.6
Work Description: !!Please CC Office Engineer Gabrielle Herrera on reports to RE and SR!! Segment 4C - Summerland: Construct HOV lanes and rehabilitation. Source inspection of sign structure trusses, lighting structures, steel soldier piles, epoxy coated rebar,
Location Description: SUMMERLAND FROM 0.2 MILES NORTH OF PARDARO LANE OVERCROSSING TO SAN YSIDRO CREEK BRIDGE
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: PO Box 6744, Santa Barbara , CA 93111
Resident Engineer: Luobao Cai Structure Rep.: Emiliano Berntsen

Sample Information

DIME Sample ID: 2020-11-11-1
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 11/11/2020
Date that the sample was received by the laboratory/organization performing the testing: 11/11/2020
The quantity of what the sample constitutes: 480
A brief description of the sample: #5 Bar HRC 120
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name: Summerland HOV lanes
The fabricator/manufacturer/facility name: Headed Reinforcement Corp, Fountain Valley, CA

Material Information

Production or Authorization Testing: Production Testing
Rebar Heat Number(s): 3098581
Head Manufacturer Lot Number(s): 100103178
Rebar Size: #5
Headed Bar Model Name: HRC 120
Size of Head: Full Size - 9x
Head Connection Type: Friction Weld
Head Shape: Square
Rebar Manufacturer: CMC Steel California
Head Manufacturer: Nucor
Head Fabricator: Headed Reinforcement Corp
Material Standard Code: ASTM A706
Headed Bar Unique ID:

Test Results

Test 1 of 6

DIME Test ID: 2020-11-11-1-1
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 11/13/2020
Date Tested: 11/13/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
10.313077499271Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 2 of 6

DIME Test ID: 2020-11-11-1-2
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 11/13/2020
Date Tested: 11/13/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
10.3131114100369Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 3 of 6

DIME Test ID: 2020-11-11-1-4
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 11/13/2020
Date Tested: 11/13/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
40.313085199518Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 4 of 6

DIME Test ID: 2020-11-11-1-5
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 11/13/2020
Date Tested: 11/13/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
40.313085199519Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 5 of 6

DIME Test ID: 2020-11-11-1-6
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 11/13/2020
Date Tested: 11/13/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
40.313084199485Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 6 of 6

DIME Test ID: 2020-11-11-1-7
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 11/13/2020
Date Tested: 11/13/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
40.313096799894Ok Neckingbewing
Temperature 72 f
UTM 400kip