Print Report | Back to Test Summary

Testing Report for 2020-07-24-2-3

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 120H1004
EFIS: 1200000180
Project ID: 208973
QA Service Level: 1
DIST-CO-RTE-PM: 12-ORA-405,73,405,605-9.3/24.3
Work Description: (Alternative Delivery) San Diego Freeway (I-405) Improvement Project SR-73 to I-605, Design Build Project, Administered by Orange County Transportation Authority, Caltrans METS to perform Source Inspection per RFP.
Location Description: Orange and Los Angeles Counties: 12-ORA-405 PM 9.3/24.2 / 07-LA-405 PM 0.0/1.2 12-ORA-22 PM R0.7/R3.8 / 12-ORA-22 PM R0.5/R0.7 12-ORA-73 PM R27.2/R27.8 / 12-ORA-605 PM 3.5/R1.6 07-LA-605 PM R0.0/R1.2
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Hank Alonso (reports)
Structure Rep.: Cal Zachman (reports)

Sample Information

DIME Sample ID: 2020-07-24-2
TL Number from the TL Form:
Sample Submitted By Organization: CT - Unassigned/General Field Laboratory
Sample Organization Contact: (510) 385-8178
Type of Sample: Quality Control
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 7/24/2020
Date that the sample was received by the laboratory/organization performing the testing: 7/30/2020
The quantity of what the sample constitutes: 62 ea.
A brief description of the sample: HRC 120 T-Heads
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: HRC

Material Information

Production or Authorization Testing: Production Testing
Rebar Heat Number(s): 3096270
Head Manufacturer Lot Number(s): B1128262
Rebar Size: #10
Headed Bar Model Name: HRC 120
Size of Head: Full Size - 9x
Head Connection Type: Friction Weld
Head Shape: Square
Rebar Manufacturer: CMC Steel California
Head Manufacturer: Nucor
Head Fabricator: Nucor
Material Standard Code: ASTM A706

Test Information

DIME Test ID: 2020-07-24-2-3
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Date Tested: 7/30/2020
Verified Date: 7/30/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test: OK Necking
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Number of Headed Bar Samples: 1
Lot # Area (sqin) Peak Load (lbf) Tensile Strength (psi) Comments Tested By
1 1.27 122419 96393 OK Necking fsaylor
Temperature: 72 f
UTM: 400kip