Project Information

Project ID: 213261 DEA: 071XH004 EFIS: 0718000239 QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-47-.86, 0.86, 0.86
Work Description: Remove and replace the two (2) long finger joint assemblies at Bents 11 and 12 and repair the elevators in both towers
Location Description:
Contractor Name: GOLDEN STATE BRIDGE INC
Contractor Address: 3701 Mallard Dr., Benicia, CA 94510
Resident Engineer: Thang Ton Structure Rep.: Noah Bruton

Sample Information

DIME Sample ID: 2019-11-26-13
TL Number from the TL Form: 1
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 11/26/2019
Date that the sample was received by the laboratory/organization performing the testing: 11/27/2019
The quantity of what the sample constitutes: 3
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 992-1
Structure unique identifier:
Structure name: VTB TOLL PLAZA
The fabricator/manufacturer/facility name: GL THROOP

Material Information

The concrete mix design number: 2017-101
The truck number from where the sample was collected: NA
The batch plant ticket number from where the sample was collected: 1
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: 1
Where the material sample would have been placed if not sampled: VTB TOLL PLAZA
From Lot No.: Unknown
Bag Lot No.: Unknown

Test Results

Test 1 of 2

DIME Test ID: 2019-11-26-13-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 12/17/2019
Date Tested: 12/10/2019
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 1
Test performed With no density determined
Cross sectional area of cylinder 1 28.27 in^2
Capped in accordance with? ASTM C617/CTM521
Compressive strength of cylinder (to nearest 10 psi) 7270 psi
Average diameter of cylinder 1 6.00 in
Maximum load on cylinder 1 205600 lb
Type of fracture pattern of cylinder 1 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Age of specimen 14 days

Test 2 of 2

DIME Test ID: 2019-11-26-13-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 01/14/2020
Date Tested: 12/24/2019
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.37 in^2
Capped in accordance with? ASTM C617/CTM521
Compressive strength (to nearest 10 psi) 7460 psi
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.01 in
Compressive strength of cylinder 1 7187.2 psi
Compressive strength of cylinder 2 7742.7 psi
Maximum load on cylinder 1 203900 lb
Maximum load on cylinder 2 219660 lb
Type of fracture pattern of cylinder 1 2
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days