Print Report | Back to Sample Detail

Sample Record for 2019-10-18-5

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 210569 DEA: 083555V4 EFIS: 0814000086 QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-15-42.5/46.0
Work Description: WIDEN I-15, RECONSTRUCT 3 IC'S, CONSTRUCT 2 NEW BR AND WIDEN 3 BR.
Location Description: SAN BERNARDINO COUNTY IN VICTORVILLE FROM 0.5 MILE NORTH OF MOJAVE DRIVE TO 1.5 MILE NORTH OF STODDARD WELLS ROAD OVERCROSSING
Contractor Name: Ames Construction
Contractor Address: 2000 AMES DRIVE, BURNSVILLE, MN 55306
Resident Engineer: Taghreed Al-Khateeb Structure Rep.: Ravinder Singh

Sample Information

DIME Sample ID: 2019-10-18-5
TL Number from the TL Form: 20191018
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 10/18/2019
Date that the sample was received by the laboratory/organization performing the testing: 10/21/2019
The quantity of what the sample constitutes: 4
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 934-1018
Structure unique identifier:
Structure name: E st and I15 Victorville
The fabricator/manufacturer/facility name: na

Material Information

The concrete mix design number: na
The truck number from where the sample was collected: na
The batch plant ticket number from where the sample was collected: na
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: SKANSKA AMES
A detailed description of where the material sample was collected: 28 cy lcb
Where the material sample would have been placed if not sampled: E st and I15 Victorville
From Lot No.: Unknown
Bag Lot No.: Unknown

Test Results

Test 1 of 1

DIME Test ID: 2019-10-18-5-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 11/04/2019
Date Tested: 10/25/2019
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.46 in^2
Capped in accordance with? ASTM C617/CTM521
Compressive strength (to nearest 10 psi) 1030 psi
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.02 in
Compressive strength of cylinder 1 1013.4 psi
Compressive strength of cylinder 2 1056.2 psi
Maximum load on cylinder 1 28750 lb
Maximum load on cylinder 2 30060 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days