Testing Report for 2019-08-21-1-2

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: No Project
EFIS:
Project ID: 0
QA Service Level:
DIST-CO-RTE-PM: ---
Work Description: Special project identifier for material not associated with a project
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown
Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2019-08-21-1
TL Number from the TL Form:
Sample Submitted By Organization: CT QASI - Los Angeles Field Laboratory
Sample Organization Contact: (858) 285-5797
Type of Sample: Acceptance
Type of Material: SMTL TM3 - Fastener Assembly
Sample Taken Date: 8/21/2019
Date that the sample was received by the laboratory/organization performing the testing: 8/26/2019
The quantity of what the sample constitutes: 3
A brief description of the sample: 7/8" x 36" A449 Hex Bolts
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: UIS Lindon UT

Material Information

Rocap Number(s): NA
Heat Number(s): 3087319
Nut Mfg. Lot Number(s): NA
Washer Mfg. Lot Number(s): NA
Bolt Specification: ASTM A449
Bolt Length(s): 36"
Nut Specification: NA
Washer Specification: NA
Finish: Hot Dip Galvanized
Diameter/Size: 7/8"
Bolt Mfg. Lot Number: 56051-1
Rocap Test Requirement(s): NA
Lubricant Requirements(s): NA

Test Information

DIME Test ID: 2019-08-21-1-2
Test Method: ASTM F606-14: Standard Test Methods for Determining the Mechanical Properties of Externally and Internally Threaded Fasteners, Washers, Direct Tension Indicators, and Rivets (Hex Cap Screws)
Date Tested: 9/6/2019
Verified Date: 9/6/2019
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test: A449 Bolt 10 Deg. Head Broke OFF
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Number of Samples: 1
Sample Size Area (in^2) Peak Load (lbf) Peak Load (kN) Tensile Strength (psi) Stress at Offset (psi) Load at Offset (lbf) Comments
2 UNC 7/8 0.462 65088 65087 1355 137229 63399 A449 Bolt 10 Deg. Head Broke OFF
UTM: 400kip
Temperature: 72