Testing Report for 2018-09-12-9-4

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 030F3514
EFIS: 0316000080
Project ID: 212726
QA Service Level: 1
DIST-CO-RTE-PM: 03-SAC-51,99-VAR
Work Description: ROADWAY EXCAVATION, HOT MIX ASPHALT AND MODIFY ELECTRICAL SYSTEM; SOLDIER PILES; CONCRETE RETAINING WALL
Location Description: SACRAMENTO COUNTY FROM 0.5 MILE SOUTH OF COSUMNES RIVER BOULEVARD TO 0.2 MILE EAST OF ARDEN WAY UNDERCROSSING
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Sushma Lee
Structure Rep.: Brent Bullard

Sample Information

DIME Sample ID: 2018-09-12-9
TL Number from the TL Form: C874455 C874456
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (916) 227-7253
Type of Sample: Quality Assurance
Type of Material: SMTL TM3 - Fastener Assembly
Sample Taken Date: 9/12/2018
Date that the sample was received by the laboratory/organization performing the testing: 9/20/2018
The quantity of what the sample constitutes: 2
A brief description of the sample: ASTM F1554 Grade 55 All Thread Rod
From where was the sample collected: Manufacturer
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Portland Bolt

Material Information

Rocap Number(s):
Heat Number(s): PL17100076 PL16207513
Nut Mfg. Lot Number(s): 28588-S-6214658903 28769-6214705402
Washer Mfg. Lot Number(s): NA
Bolt Specification: F1554
Bolt Length(s): 10.5 10
Nut Specification: A563
Washer Specification: NA
Finish: HDG
Diameter/Size: .875 .75
Bolt Mfg. Lot Number:
Rocap Test Requirement(s):
Lubricant Requirements(s):

Test Information

DIME Test ID: 2018-09-12-9-4
Test Method: ASTM F606-14a: Standard Test Methods for Determining the Mechanical Properties of Externally and Internally Threaded Fasteners, Washers, Direct Tension Indicators, and Rivets (Proof Load)
Date Tested: 9/26/2018
Verified Date: 9/26/2018
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test: Nut Proof Load
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Number of Samples: 1
Sample Bolt Mfg. Lot Number Size (in) Peak Load (lbf) Peak Load (kN) Comments Tested By
2A 28769-6214705402 ?\" 50817 226.05 Nut Proof Load Brian
UTM: 400KIP
Temperature: 72 F