Print Report | Back to Test Summary

Testing Report for 2018-07-13-1-6

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 06471504
EFIS: 0600000464
Project ID: 209146
QA Service Level: 1
DIST-CO-RTE-PM: 06-TUL-99-39.6/41.3
Work Description: RECONSTRUCT INTERCHANGE WITH NEW PUMPING PLANT.
Location Description: TULARE COUNTY AT GOSHEN FROM 0.9 MILE NORTH OF ROUTE 99/198 WEST SEPARATION TO 0.2 MILE NORTH OF NORTH GOSHEN OVERHEAD
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Brent Haroldsen
Structure Rep.: Peter Moua

Sample Information

DIME Sample ID: 2018-07-13-1
TL Number from the TL Form: Unknown
Sample Submitted By Organization: CT QASI - Bay Area Field Laboratory
Sample Organization Contact: (707) 649-5453
Type of Sample: Acceptance
Type of Material: SMTL TM3 - Fastener Assembly
Sample Taken Date: 7/13/2018
Date that the sample was received by the laboratory/organization performing the testing: 7/19/2018
The quantity of what the sample constitutes: various lots
A brief description of the sample: A325 HDG Rocap Assembiy
From where was the sample collected: Fabricator
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Structural and Steel Products

Material Information

Rocap Number(s):
Heat Number(s): see tl102
Nut Mfg. Lot Number(s): See TL102
Washer Mfg. Lot Number(s): 1/2 D1214 5/8 D1703 3/4 309270 1 1/4 0415-828 1 1/2 C7027M
Bolt Specification: ASTM A 325
Bolt Length(s): 1 3/4 to 4 1/2
Nut Specification: ASTM A536
Washer Specification: ASTM F436
Finish: Mechanical Galv
Diameter/Size: 1/2 to 1 1/2
Bolt Mfg. Lot Number: 1/2 x 2 3/4 M4163 5/8 x 2 BM0324 3/4 x 2 1/
Rocap Test Requirement(s): Yes
Lubricant Requirements(s): Yes

Test Information

DIME Test ID: 2018-07-13-1-6
Test Method: ASTM F606-14a: Standard Test Methods for Determining the Mechanical Properties of Externally and Internally Threaded Fasteners, Washers, Direct Tension Indicators, and Rivets (Proof Load with Wedge)
Date Tested: 7/26/2018
Verified Date: 7/31/2018
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test: A325
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Number of Bolt Samples: 1
Sample Bolt Mfg. Lot Number Size (in) Peak Load (lbf) Peak Load (kN) Wedge Angle (deg) Comments Tested By
3A M3211 3/4\" 45150 200.8 10 A325 Fred
UTM: 400KIP
Temperature: no data