Testing Report for 2018-07-19-1-3

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 044G0564
EFIS: 0417000154
Project ID: 212618
QA Service Level: 1
DIST-CO-RTE-PM: 04-ALA-680-M2.4/M12.4
Work Description: ROADWAY REHAB, BRIDGE REPLACEMENT, RET. WALLS, TOLL SYSTEMS
Location Description: FREMONT AND AT SUNOL FROM MISSION BOULEVARD SEPARATION TO KOOPMAN ROAD UNDERCROSSING
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Yannaing Tun
Structure Rep.: Jordan Jarosz

Sample Information

DIME Sample ID: 2018-07-19-1
TL Number from the TL Form:
Sample Submitted By Organization: CT - Unassigned/General Field Laboratory
Sample Organization Contact: (510) 385-8178
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 7/19/2018
Date that the sample was received by the laboratory/organization performing the testing:
The quantity of what the sample constitutes: 150
A brief description of the sample: Bar Lock Couplers
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Harris Rebar

Material Information

Production or Authorization Testing: Production Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Nucor
Coupler Manufacturer: Dayton Superior
Intermediate Assembler or Fabricator: Ramon Tapia
Rebar Size: 8
Coupler Model: Bar Lock Standard
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): A152317
Rebar Heat Number(s): SE18101740
Rebar Size 2 :

Test Information

DIME Test ID: 2018-07-19-1-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Date Tested: 7/23/2018
Verified Date: 7/23/2018
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Number of Samples: 1
Sample Mfg. Lot Number(s) Size Area (sqin) Slip (inch) Peak Load (lbf) Peak Stress (psi) Comments Tested By
3 C01 #8/25mm 0.79 0 73725 93323 Service Splice Fred
Temperature: 72 F
UTM: 400KIP
Halo ID: Small