Testing Report for 2018-07-05-8-3

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 024G2404
EFIS: 0213000095
Project ID: 212681
QA Service Level: 1
DIST-CO-RTE-PM: 02-SIS-5-R25.2
Work Description: STRENGTHEN AND UPGRADE BRIDGES.
Location Description: SISKIYOU COUNTY ABOUT 5 MILES NORTH OF WEED AT THE NORTH EDGEWOOD OVERHEAD
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Jeff Steppat
Structure Rep.: Russell Cox

Sample Information

DIME Sample ID: 2018-07-05-8
TL Number from the TL Form: C980903
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (916) 227-7253
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 7/5/2018
Date that the sample was received by the laboratory/organization performing the testing: 7/11/2018
The quantity of what the sample constitutes: 4
A brief description of the sample: Bar Lock Standard Couplers
From where was the sample collected: Job Site
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Dayton Superior

Material Information

Production or Authorization Testing: Authorization Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: NA
Coupler Manufacturer: Dayton Superior
Intermediate Assembler or Fabricator: Unknown
Rebar Size: 8
Coupler Model: Bar Lock
Coating Standards: ASTM A775
Shape of Rebar: Straight
Rebar Hoop Diameter: Unknown
Rebar Hoop Fabricator: Unknown
Coupler Component Heat/Lot Number(s): A152317 A150815
Rebar Heat Number(s): NA
Rebar Size 2 :

Test Information

DIME Test ID: 2018-07-05-8-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Date Tested: 7/11/2018
Verified Date: 7/11/2018
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Number of Samples: 1
Sample Mfg. Lot Number(s) Size Area (sqin) Slip (inch) Peak Load (lbf) Peak Stress (psi) Comments Tested By
3 1 #8/25mm 0.79 0 76849 97277 Service Splice Brian
Temperature: 72 F
UTM: 400KIP
Halo ID: Small