Testing Report for 2018-06-30-8-2

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 020E1804
EFIS: 0200000022
Project ID: 212741
QA Service Level: 1
DIST-CO-RTE-PM: 02-PLU-89-29.8/30.2
Work Description: BRIDGE REPLACEMENT
Location Description: PLUMAS COUNTY NEAR CANYON DAM FROM 0.2 MILE SOUTH TO 0.3 MILE NORTH OF LAKE ALMANOR SPILLWAY
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Ryan Johnson
Structure Rep.: Matt Crete

Sample Information

DIME Sample ID: 2018-06-30-8
TL Number from the TL Form: C931426 C931428
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (916) 227-7253
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 6/30/2018
Date that the sample was received by the laboratory/organization performing the testing: 7/2/2018
The quantity of what the sample constitutes: 8
A brief description of the sample: Couplers
From where was the sample collected: Manufacturer
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Confab HRC

Material Information

Production or Authorization Testing: Production Testing
Service or Ultimate: Ultimate
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: CMC
Coupler Manufacturer: HRC
Intermediate Assembler or Fabricator: Confab HRC
Rebar Size: 10
Coupler Model: HRC 500 510
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter: Unknown
Rebar Hoop Fabricator: Unknown
Coupler Component Heat/Lot Number(s): 75070365, 75069694
Rebar Heat Number(s): 4073764
Rebar Size 2 :

Test Information

DIME Test ID: 2018-06-30-8-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Date Tested: 7/2/2018
Verified Date: 7/3/2018
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test: necking okay
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Number of Samples: 1
Sample Mfg. Lot Number(s) Size Area (sqin) Slip (inch) Peak Load (lbf) Peak Stress (psi) Comments Tested By
2 1 #10/32mm 1.27 0 117374 92420 necking okay Brian
Temperature: 72 F
UTM: 2000KIP
Halo ID: Big