Testing Report for 2018-06-04-3-2

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 030H26U4
EFIS: 0317000247
Project ID: 212743
QA Service Level: 1
DIST-CO-RTE-PM: 03-PLA-65-R5.0/R6.6
Work Description: NORTHBOUND WIDENING AND RAMP IMPROVEMENTS.
Location Description: PLACER COUNTY IN AND NEAR ROSEVILLE AND ROCKLIN FROM 0.1 MILE SOUTH OF EAST ROSEVILLE VIADUCT TO 0.5 MILE SOUTH OF PLEASANT GROVE BOULEVARD OVERCROSSING
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Jeff Johnson
Structure Rep.: James "Jimmer" Ross

Sample Information

DIME Sample ID: 2018-06-04-3
TL Number from the TL Form: C710752
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (916) 227-7253
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 6/4/2018
Date that the sample was received by the laboratory/organization performing the testing: 6/4/2018
The quantity of what the sample constitutes: 150
A brief description of the sample: size 9 HRC 501 510 couplers
From where was the sample collected: Job Site
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: HRC

Material Information

Production or Authorization Testing: Authorization Testing
Service or Ultimate: Ultimate
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: CMC
Coupler Manufacturer: HRC
Intermediate Assembler or Fabricator: Unknown
Rebar Size: 9
Coupler Model: HRC 501/510
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter: Unknown
Rebar Hoop Fabricator: Unknown
Coupler Component Heat/Lot Number(s): A162514
Rebar Heat Number(s): 4073721
Rebar Size 2 :

Test Information

DIME Test ID: 2018-06-04-3-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Date Tested: 6/6/2018
Verified Date: 6/6/2018
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test: OK Necking
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Number of Samples: 1
Sample Mfg. Lot Number(s) Size Area (sqin) Slip (inch) Peak Load (lbf) Peak Stress (psi) Comments Tested By
2 1 #9/29mm 1 0 94520 94520 OK Necking Fred
Temperature: 72 F
UTM: 400KIP
Halo ID: Small