Print Report | Back to Test Summary

Testing Report for 2017-08-04-2-1

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 07288604
EFIS: 0700021080
Project ID: 208945
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-710-6.0-9.4
Work Description: Gerald Desmond Bridge Replacement - A Design Build project. IQA samples will be selected by Port/Caltrans representatives and sent to Translab for testing.
Location Description: Port of Long Beach (District 7)
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer:
Structure Rep.:

Sample Information

DIME Sample ID: 2017-08-04-2
TL Number from the TL Form: Unknown
Sample Submitted By Organization: CT - Unassigned/General Field Laboratory
Sample Organization Contact: (510) 385-8178
Type of Sample: Quality Assurance
Type of Material: SMTL TM4 - Prestressing Strand
Sample Taken Date: 8/4/2017
Date that the sample was received by the laboratory/organization performing the testing: 8/7/2017
The quantity of what the sample constitutes: 14 packs
A brief description of the sample: 6/10 x 270 KSI Strand
From where was the sample collected: Manufacturer
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Sumiden Wire

Material Information

Comments: Unknown
Reel/Coil/Pack Number(s): S334180-4
Number of Coils: 1
Group Number: Unknown
Strand Diameter: .6 in
Grade: 270
Strand Specification: ASTM A 416
Heat Number(s): S0520317
Mfg. Lot Number(s): SIPC171928
Manufacturer(s): Suniden

Test Information

DIME Test ID: 2017-08-04-2-1
Test Method: ASTM A416-15: Standard Specification for Low-Relaxation, Seven-Wire Steel Strand for Prestressed Concrete
Date Tested: 8/8/2017
Verified Date: 8/8/2017
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Number of Samples: 1
Heat Number Coil Area (sqin) Peak Load (lbf) Load at EUL (lbf) Chord Modulus (Msi) Elongation (in) Tested By
S0520317 S334180-4 0.215 58851 54579 28 1.85 Brian
UTM: 120KIP
Temperature: 72 F
Extensometers: E88766