Sample Record for 2017-06-13-6

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 208945 DEA: 07288604 EFIS: 0700021080 COOP: 074663 QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-710-6.0-9.4
Work Description: Gerald Desmond Bridge Replacement - A Design Build project. IQA samples will be selected by Port/Caltrans representatives and sent to Translab for testing.
Location Description: Port of Long Beach (District 7)
Contractor Name: Shimmick/FCC/Impregilo (SFI) JV
Contractor Address: 11 Golden Shore, Suite 330, Long Beach, CA 90802
Resident Engineer: Structure Rep.:

Sample Information

DIME Sample ID: 2017-06-13-6
TL Number from the TL Form: C969300
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 06/13/2017
Date that the sample was received by the laboratory/organization performing the testing: 06/16/2017
The quantity of what the sample constitutes: 4
A brief description of the sample: Headed Bars
From where was the sample collected: Fabricator
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CMC Rebar

Material Information

Production or Authorization Testing: Authorization Testing
Rebar Heat Number(s): 289415
Head Manufacturer Lot Number(s): 1
Rebar Size: 14
Headed Bar Model Name: HRC 555
Size of Head: Reduced Size - 4x
Head Connection Type: Forged
Head Shape: Circular
Rebar Manufacturer: CMC
Head Manufacturer: HRC
Head Fabricator: HRC
Material Standard Code: ASTM A706
Headed Bar Unique ID:

Test Results

Test 1 of 3

DIME Test ID: 2017-06-13-6-1
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 06/20/2017
Date Tested: 06/20/2017
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke; OK Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
12.2521180094130Bar BrokeBrian
Temperature 71 F
UTM 2000KIP

Test 2 of 3

DIME Test ID: 2017-06-13-6-2
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 06/20/2017
Date Tested: 06/20/2017
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke; OK Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
12.2521065093620Bar BrokeBrian
Temperature 71 F
UTM 2000KIP

Test 3 of 3

DIME Test ID: 2017-06-13-6-3
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 06/20/2017
Date Tested: 06/20/2017
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke; OK Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
12.2521285094600Bar BrokeBrian
Temperature 71 F
UTM 2000KIP