Print Report | Back to Test Summary

Testing Report for 2017-01-10-6-10

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 59912684
EFIS:
Project ID: 8196
QA Service Level: 1
DIST-CO-RTE-PM: 59---
Work Description:
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown
Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2017-01-10-6
TL Number from the TL Form: NA
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (916) 227-7253
Type of Sample: Quality Assurance
Type of Material: SMTL TM4 - Prestressing Strand
Sample Taken Date: 1/10/2017
Date that the sample was received by the laboratory/organization performing the testing: 1/13/2017
The quantity of what the sample constitutes: 79
A brief description of the sample: Prestressing Strand Group 10855
From where was the sample collected: Manufacturer
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Sumiden Wire

Material Information

Comments: Unknown
Reel/Coil/Pack Number(s):
Number of Coils: Unknown
Group Number: 10855
Strand Diameter: .6 in
Grade: 270
Strand Specification: ASTM A 416
Heat Number(s): S0534116, S0577516, S0534916, S0535016, S0577416, S0534016, S0577616, S0534216, S0534816, S0534716, S0535116, S0577716, S0534316, S0577316, S0534416, S0288054, S0534516,
Mfg. Lot Number(s): NA
Manufacturer(s): Sumiden Wire

Test Information

DIME Test ID: 2017-01-10-6-10
Test Method: ASTM A416-15: Standard Specification for Low-Relaxation, Seven-Wire Steel Strand for Prestressed Concrete
Date Tested: 1/17/2017
Verified Date: 1/23/2017
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Number of Samples: 1
Heat Number Coil Area (sqin) Peak Load (lbf) Load at EUL (lbf) Chord Modulus (Msi) Elongation (in) Tested By
S0577416 S333896-5 0.215 59539 54730 28.5 1.86 Brian
UTM: 120KIP
Temperature: 72 F
Extensometers: E88766