Contract # 044J6304 Cty SOL Rte 80 PM 17.2 Vendor # |
REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Quang Tran |
Date Reported: |
12/07/2016 |
|
Address: |
TL Number: |
209658 |
||
City: |
||||
Project Name: BUILD MATERIALS STORAGE BINS WITH CANOPY. |
||||
Prime Contractor: NORTHSTATE EARTH AND WATER INC. |
||||
Sample Taken Date: |
11/09/2016 |
Mix Design: |
z5725200 |
|
Contractor: Unknown |
Location: SOLANO COUNTY IN FAIRFIELD MAINTENANCE STATION 2019 WEST TEXAS STREET |
|||
Structure unique identifier: Unknown |
||||
Structure name: Unknown |
||||
Location of Pour: Unknown |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 5.94 | 27.71 | 132158 | 4769.3 | 1 |
2 | 5.97 | 27.99 | 154160 | 5507.7 | 4 |
DIME Test ID: 2016-11-09-3-1
Number of specimens: 2
Compressive strength (to nearest 10 psi): 5140
Age of specimen: 28 days
Certified By: Bang Nguyen
*Subject to final inspection by the Resident Engineer. |
TL- Report of Laboratory Testing