Print Report | Back to Test Summary

Testing Report for 2016-09-09-6-2

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 080M2804
EFIS: 0800000472
Project ID: 210696
QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-15-171.8/173.8
Work Description: BRIDGE REPLACEMENT AND WIDEN, CONC AND HMA PVMT, COLD PLANE AC PVMT.
Location Description: In SBD County
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: John Santos
Structure Rep.: Faisal Zahlout

Sample Information

DIME Sample ID: 2016-09-09-6
TL Number from the TL Form: 942-05
Sample Submitted By Organization: CT - Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 9/9/2016
Date that the sample was received by the laboratory/organization performing the testing: 9/9/2016
The quantity of what the sample constitutes: 8
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 942-05
Structure unique identifier: Unknown
Structure name: Unknown
The fabricator/manufacturer/facility name: Jobsite

Material Information

The concrete mix design number: P40F023
The truck number from where the sample was collected: A031
The batch plant ticket number from where the sample was collected: S485389
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: Dischard fron concrete truck into wheelbarrow.
Where the material sample would have been placed if not sampled: jobsite
From Lot No.: Unknown
Bag Lot No.: Unknown

Test Information

DIME Test ID: 2016-09-09-6-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Date Tested: 9/30/2016
Capped in accordance with: ASTM C617/CTM521
Verified Date: 10/3/2016
Submitted By Organization: CT - Southern Regional Laboratory
Organization Address: 13970 Victoria St,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 213-792-4794
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Cross sectional area of cylinder 1: 28.18 in^2
Cross sectional area of cylinder 2: 28.18 in^2
Capped in accordance with?: ASTM C617/CTM521
Compressive strength (to nearest 10 psi): 5510 psi
Average diameter of cylinder 1: 5.99 in
Average diameter of cylinder 2: 5.99 in
Compressive strength of cylinder 1: 5509.2 psi
Compressive strength of cylinder 2: 5509.9 psi
Maximum load on cylinder 1: 155250 lb
Maximum load on cylinder 2: 155270 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: no data
Age of specimen: 21 days