Project Information

Project ID: 209916 DEA: 07259024 EFIS: 0713000046 QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-5,10,91,110,134-Var
Work Description: INSTALL AUSTIN VAULT SAND FILTERS AND BIOFILTRATION SWALE AND STRIPS
Location Description: LOS ANGELES COUNTY AT VARIOUS LOCATIONS
Contractor Name: Ortiz Enterprise, Inc
Contractor Address: 6 Cushing Suite 200, Irvine, CA 92618
Resident Engineer: Sam Gallardo Structure Rep.: Adriana Pimienta

Sample Information

DIME Sample ID: 2016-02-10-6
TL Number from the TL Form: 185013
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 02/10/2016
Date that the sample was received by the laboratory/organization performing the testing: 02/23/2016
The quantity of what the sample constitutes: 4
A brief description of the sample: 6x12
From where was the sample collected: Job Site
Laboratory sample identification: 9003-13
Structure unique identifier: avsf footing at loc 7 system 13f
Structure name: Unknown
The fabricator/manufacturer/facility name: Associated Ready Mix

Material Information

The concrete mix design number: 556300
The truck number from where the sample was collected: load1
The batch plant ticket number from where the sample was collected: 40237190
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: chute
Where the material sample would have been placed if not sampled: Unknown
From Lot No.: Unknown
Bag Lot No.: Unknown

Test Results

Test 1 of 2

DIME Test ID: 2016-02-10-6-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 03/09/2016
Date Tested: 03/09/2016
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.01 in
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.37 in^2
Compressive strength (to nearest 10 psi) 4100 psi
Maximum load on cylinder 1 113200 lb
Maximum load on cylinder 2 119550 lb
Compressive strength of cylinder 1 3990.1 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 4214.0 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Age of specimen 28 days
Age of specimen in hours no data

Test 2 of 2

DIME Test ID: 2016-02-10-6-2
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 03/24/2016
Date Tested: 03/23/2016
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 6.00 in
Average diameter of cylinder 2 6.00 in
Cross sectional area of cylinder 1 28.27 in^2
Cross sectional area of cylinder 2 28.27 in^2
Compressive strength (to nearest 10 psi) 4670 psi
Maximum load on cylinder 1 131650 lb
Maximum load on cylinder 2 132400 lb
Compressive strength of cylinder 1 4656.9 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 4683.4 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Age of specimen 42 days
Age of specimen in hours no data