Project ID: 210307 DEA: 073P7004 EFIS: 0712000437
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-L5724-
Work Description: CONSTRUCT MAINTENANCE STATION
Location Description: VENTURA COUNTY IN OJAI AT THE OJAI MAINTENANCE STATION AT 1116 MARICOPA HIGHWAY
Contractor Name: MPG Construction
Contractor Address: PO Box 355, Upland, CA 91785
Resident Engineer: Hussam Buran Structure Rep.: Aziz Maghsoudloo
DIME Sample ID: 2015-10-20-5
TL Number from the TL Form: 053649
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 10/20/2015
Date that the sample was received by the laboratory/organization performing the testing: 10/27/2015
The quantity of what the sample constitutes: 4
A brief description of the sample: 6X12
From where was the sample collected: Job Site
Laboratory sample identification: 921-49
Structure unique identifier: OJAI MS BLDG
Structure name: Unknown
The fabricator/manufacturer/facility name: ASSOCIATED READY MIX
The concrete mix design number: 55630
The truck number from where the sample was collected: LOAD 2
The batch plant ticket number from where the sample was collected: NP
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: LOAD 2
Where the material sample would have been placed if not sampled: Unknown
From Lot No.:
Bag Lot No.:
DIME Test ID: 2015-10-20-5-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/10/2015
Date Tested: 11/10/2015
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Compressive strength (to nearest 10 psi)
|
3590 psi
|
Maximum load on cylinder 1
|
103160 lb
|
Maximum load on cylinder 2
|
99780 lb
|
Compressive strength of cylinder 1
|
3649.1 psi
|
Type of fracture pattern of cylinder 1
|
1
|
Compressive strength of cylinder 2
|
3529.5 psi
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
21 days
|
Age of specimen in hours
|
no data
|
DIME Test ID: 2015-10-20-5-2
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/17/2015
Date Tested: 11/17/2015
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Compressive strength (to nearest 10 psi)
|
4030 psi
|
Maximum load on cylinder 1
|
113130 lb
|
Maximum load on cylinder 2
|
114610 lb
|
Compressive strength of cylinder 1
|
4001.8 psi
|
Type of fracture pattern of cylinder 1
|
1
|
Compressive strength of cylinder 2
|
4054.1 psi
|
Type of fracture pattern of cylinder 2
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
no data
|