Print Report | Back to Sample Detail

Sample Record for 2021-08-30-46

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 215333 DEA: 120S6604 EFIS: 1221000004 QA Service Level: 1
DIST-CO-RTE-PM: 12-ORA-91-R16.6/R17.0
Work Description: COLD PLANE AC PAVEMENT AND PLACE PRECAST CONCRETE PAVEMENT.
Location Description: ORANGE COUNTY IN YORBA LINDA FROM W91-S241/91 CONNECTOR SEPARATION TO 0.6 MILE EAST OF GYPSUM CANYON ROAD UNDERCROSSING
Contractor Name: BEADOR CONSTRUCTION COMPANY, INC.
Contractor Address: 26320 LESTER CIRCLE, CORONA CA 92883
Resident Engineer: Adrian Wu Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2021-08-30-46
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Quality Assurance
Type of Material: SMTL TM4 - Prestressing Strand
Sample Taken Date: 08/30/2021
Date that the sample was received by the laboratory/organization performing the testing: 09/03/2021
The quantity of what the sample constitutes: 10
A brief description of the sample: .5 Prestressing Strand
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Sumiden Wire

Material Information

Comments:
Reel/Coil/Pack Number(s):
Number of Coils:
Group Number:
Strand Diameter: .5 in
Grade: 270
Strand Specification: ASTM A 416
Heat Number(s): S0571221-3, S0563921, S0563721
Mfg. Lot Number(s): NA
Manufacturer(s): Sumiden Wire

Test Results

Test 1 of 6

DIME Test ID: 2021-08-30-46-1
Test Method: ASTM A416-15: Standard Specification for Low-Relaxation, Seven-Wire Steel Strand for Prestressed Concrete
Verified Date: 09/23/2021
Date Tested: 09/23/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
Heat NumberCoilArea (sqin)Peak Load (lbf)Load at EUL (lbf)Chord Modulus (Msi)Elongation (in)Tested By
S0571221-3S533431-20.1534210539219.628.31.91bewing
UTM 120kip
Temperature 72 f
Extensometers no data

Test 2 of 6

DIME Test ID: 2021-08-30-46-2
Test Method: ASTM A416-15: Standard Specification for Low-Relaxation, Seven-Wire Steel Strand for Prestressed Concrete
Verified Date: 09/23/2021
Date Tested: 09/23/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
Heat NumberCoilArea (sqin)Peak Load (lbf)Load at EUL (lbf)Chord Modulus (Msi)Elongation (in)Tested By
S0571221-3S533431-30.1534222739862.828.41.72bewing
UTM 120kip
Temperature 72 f
Extensometers no data

Test 3 of 6

DIME Test ID: 2021-08-30-46-3
Test Method: ASTM A416-15: Standard Specification for Low-Relaxation, Seven-Wire Steel Strand for Prestressed Concrete
Verified Date: 09/23/2021
Date Tested: 09/23/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
Heat NumberCoilArea (sqin)Peak Load (lbf)Load at EUL (lbf)Chord Modulus (Msi)Elongation (in)Tested By
S0563921S533432-10.1534214839760.528.51.69bewing
UTM 120kip
Temperature 72 f
Extensometers no data

Test 4 of 6

DIME Test ID: 2021-08-30-46-4
Test Method: ASTM A416-15: Standard Specification for Low-Relaxation, Seven-Wire Steel Strand for Prestressed Concrete
Verified Date: 09/23/2021
Date Tested: 09/23/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
Heat NumberCoilArea (sqin)Peak Load (lbf)Load at EUL (lbf)Chord Modulus (Msi)Elongation (in)Tested By
S0563921S533432-20.1534230339789.3291.85bewing
UTM 120kip
Temperature 72 f
Extensometers no data

Test 5 of 6

DIME Test ID: 2021-08-30-46-5
Test Method: ASTM A416-15: Standard Specification for Low-Relaxation, Seven-Wire Steel Strand for Prestressed Concrete
Verified Date: 09/23/2021
Date Tested: 09/23/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
Heat NumberCoilArea (sqin)Peak Load (lbf)Load at EUL (lbf)Chord Modulus (Msi)Elongation (in)Tested By
S0563721S533433-10.1534215239619.128.41.82bewing
UTM 120kip
Temperature 72 f
Extensometers no data

Test 6 of 6

DIME Test ID: 2021-08-30-46-6
Test Method: ASTM A416-15: Standard Specification for Low-Relaxation, Seven-Wire Steel Strand for Prestressed Concrete
Verified Date: 09/23/2021
Date Tested: 09/23/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
Heat NumberCoilArea (sqin)Peak Load (lbf)Load at EUL (lbf)Chord Modulus (Msi)Elongation (in)Tested By
S0563721S533433-20.1534215739507.328.51.88bewing
UTM 120kip
Temperature 72 f
Extensometers no data