Print Report | Back to Test Summary

Testing Report for 2021-09-07-9-2

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 033F5604
EFIS: 0313000033
Project ID: 212252
QA Service Level: 1
DIST-CO-RTE-PM: 03-SUT,YUB-20-17.0/17.1,0.0/0.4
Work Description: INSTALL CAST-IN-STEEL SHELL CONCRETE PILE.
Location Description: SUTTER AND YUBA COUNTIES IN YUBA CITY AND MARYSVILLE AT THE FEATHER RIVER BRIDGE AND OVERHEAD
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Selvendran Manoharan
Structure Rep.: Brent Bullard

Sample Information

DIME Sample ID: 2021-09-07-9
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (916) 227-7253
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 9/7/2021
Date that the sample was received by the laboratory/organization performing the testing: 9/8/2021
The quantity of what the sample constitutes: 150 Couplers
A brief description of the sample: Zap Screwlock Type 2 Couplers
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: C and N Reinforcing

Material Information

Production or Authorization Testing: Production Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Nucor
Coupler Manufacturer: BarSplice
Intermediate Assembler or Fabricator:
Rebar Size: #5
Coupler Model: Zap Screwlok Type 2
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): A205906
Rebar Heat Number(s): 3500019256
Rebar Size 2 :

Test Information

DIME Test ID: 2021-09-07-9-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Date Tested: 9/9/2021
Verified Date: 9/9/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Number of Samples Tested: 1
Sample Number of Cycles Size Mfg. Lot Number(s) Slip (inch) Area (sqin) Peak Load (lbf) Peak Stress (psi) Comments Tested By
2 No. 5/16mm 1 0 0.31 29077 93798 Service Splice fsaylor
UTM: 400kip
Temperature: 72.00 f
Halo ID: