Project ID: 214426 DEA: 030A5704 EFIS: 0300020593
QA Service Level: 1
DIST-CO-RTE-PM: 03-YUB-20-13.3/R18.2
Work Description: Browns Valley Rehab: CONSTRUCT BRIDGE, REALIGN CURVE, WIDEN SHOULDERS AND CULVERT WORK.
Location Description: YUBA COUNTY FROM MARYSVILLE ROAD TO THE YUBA RIVER BRIDGE
Contractor Name: A. TEICHERT & SON, INC. DBA TEICHERT CONSTRUCTION
Contractor Address: 400 Sunrise Ave, Suite 300, Roseville, CA 95661
Resident Engineer: Garrett Griffith Structure Rep.: Matt Crete
DIME Sample ID: 2021-07-14-22
TL Number from the TL Form: 597105
Sample Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Sample Organization Contact: (916) 227-7302
Type of Sample: Acceptance
Type of Material: Asphalt Binder
Sample Taken Date: 07/14/2021
Date that the sample was received by the laboratory/organization performing the testing: 07/26/2021
The quantity of what the sample constitutes: 1 Can
A brief description of the sample: PG 64-16 Marathon
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Teichert - Hallwood Plant
Performance Grade: PG 64-16
Modified:
Lot number: 6
Sublot number: 8
Tank number:
Time of sample:
HMA Supplier:
Certified Asphalt Supplier: Marathon Petroleum Co. LP - Elk Grove CA
Multigrade: No
Multigrade Type:
Asphalt Binder Mix Number:
DIME Test ID: 2021-07-14-22-1
Test Method: AASHTO T240-17: Standard Method of Test for Effect of Heat and Air on a Moving Film of Asphalt Binder (Rolling Thin-Film Oven Test)
Verified Date: 08/04/2021
Date Tested: 08/01/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications
Test Result Compliance: complies
Additional Comments When Verified:
Is mass change based on one or two containers?
|
Two
|
Any material loss from containers during heating process/testing?
|
No
|
Mass of empty container #1
|
156.015 grams
|
Mass of empty container #2
|
171.225 grams
|
Mass of container #1 before test (m1i)
|
192.077 grams
|
Mass of container #2 before test (m2i)
|
207.071 grams
|
Mass of container #1 after test (m1f)
|
191.928 grams
|
Mass of container #2 after test (m2f)
|
206.963 grams
|
Average mass change
|
-0.357 percent
|
DIME Test ID: 2021-07-14-22-2
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 08/04/2021
Date Tested: 08/01/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: 2018 Standard Specifications OG
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
Original binder
|
Test Plate Diameter
|
25 mm
|
Test Gap
|
1 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
12.00 %
|
Stress Amplitude
|
0.178 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
87.2 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
1.487 kPa
|
Test Temperature (Specimen 1)
|
64.0 C
|
Dynamic Shear, G*/sin(δ)
|
1.49 kPa
|
DIME Test ID: 2021-07-14-22-3
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 08/04/2021
Date Tested: 08/01/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications RTFO
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
RTFO residue
|
Test Plate Diameter
|
25 mm
|
Test Gap
|
1 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
10.00 %
|
Stress Amplitude
|
0.451 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
83.4 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
4.507 kPa
|
Test Temperature (Specimen 1)
|
64.0 C
|
Dynamic Shear, G*/sin(δ)
|
4.54 kPa
|
DIME Test ID: 2021-07-14-22-4
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 08/04/2021
Date Tested: 08/02/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications PAV
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
PAV residue
|
Test Plate Diameter
|
8 mm
|
Test Gap
|
2 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
1.00 %
|
Stress Amplitude
|
42.051 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
49.5 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
4205.159 kPa
|
Test Temperature (Specimen 1)
|
28.0 C
|
(G*) x sin(δ)=
|
3198 kPa
|
DIME Test ID: 2021-07-14-22-5
Test Method: AASHTO T313-19: Standard Method of Test for Determining the Flexural Creep Stiffness of Asphalt Binder Using the Bending Beam Rheometer (BBR)
Verified Date: 08/04/2021
Date Tested: 08/02/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: per 2018 standard specifications
Test Result Compliance: complies
Additional Comments When Verified:
Minimum test bath temperature at 240 s
|
-6.0 C
|
Maximum test bath temperature at 240 s
|
-6.0 C
|
Time of test load application
|
no data HH:MM:SS
|
File name of test data
|
no data
|
Time beam in bath
|
no data
|
Time test started
|
no data HH:MM:SS
|
Flags issued by software during test
|
no data
|
Correlation coefficient (R²)
|
0
|
Regression coefficient a
|
no data
|
Regression coefficient b
|
no data
|
Regression coefficient c
|
no data
|
Load at time 0.0
|
0.0 mN
|
Deflection at time 0.0 s
|
0.000 µm
|
Load at time 0.5 s
|
0.0 mN
|
Deflection at time 0.5 s
|
0.000 µm
|
Load at 60.0 s
|
996.0 mN
|
Beam deflection 60.0 s
|
1.025 µm
|
Measured Stiffness Modulus 60.0 s
|
78.300 mPa
|
Estimated Stiffness Modulus 60.0 s
|
78.300 mPa
|
Difference between stiffness moduli 60.0 s
|
no data
|
Estimated m-value 60.0 s
|
0.409
|