Print Report | Back to Sample Detail

Sample Record for 2021-07-08-20

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 214422 DEA: 040J6424 EFIS: 0414000476 QA Service Level: 1
DIST-CO-RTE-PM: 04-SON-101-32.8/R54.2
Work Description: CRACK, SEAT AND OVERLAY WITH RHMA AND HMA, AND REPLACE CULVERTS.
Location Description: SONOMA COUNTY AT VARIOUS LOCATIONS FROM LIMERICK LANE OVERCROSSING TO ROUTE 101/128 SEPARATION
Contractor Name: O.C. JONES & SONS, INC.
Contractor Address: 1520 FOURTH STREET, BERKELY, CA 94710
Resident Engineer: Syd Valeh Structure Rep.: Jonathan Chi

Sample Information

DIME Sample ID: 2021-07-08-20
TL Number from the TL Form:
Sample Submitted By Organization: Oldcastle Precast, Incorporated - Pleasanton
Sample Organization Contact: (925) 846-8183
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 07/08/2021
Date that the sample was received by the laboratory/organization performing the testing: 07/08/2021
The quantity of what the sample constitutes: 2.8 CY
A brief description of the sample: SCC concrete
From where was the sample collected: Manufacturer
Laboratory sample identification: 21147
Structure unique identifier: 04-son-101-32.8/R54.2
Structure name: State Hwy in Sonoma County 101/128 Separation
The fabricator/manufacturer/facility name: Oldcastle Infrastructure

Material Information

The concrete mix design number: 55
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 93274
Concrete batch plant: Oldcastle Infrastructure
The fabricator/manufacturer designation for the sample: Mix No. 55
A detailed description of where the material sample was collected: Travelling Bucket
Where the material sample would have been placed if not sampled: RBC
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 7

DIME Test ID: 2021-07-08-20-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 07/09/2021
Date Tested: 07/08/2021
Submitted By Organization: Oldcastle Precast, Incorporated - Pleasanton
Organization Address: 1233 Quarry Lane, Suite 145,
Organization City: Pleasanton
Organization State: CA
Organization Zipcode: 94566
Organization Email: juan.maiz@oldcastle.com
Organization Phone: (925) 750-6646
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Temperature 75 F

Test 2 of 7

DIME Test ID: 2021-07-08-20-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 07/09/2021
Date Tested: 07/08/2021
Submitted By Organization: Oldcastle Precast, Incorporated - Pleasanton
Organization Address: 1233 Quarry Lane, Suite 145,
Organization City: Pleasanton
Organization State: CA
Organization Zipcode: 94566
Organization Email: juan.maiz@oldcastle.com
Organization Phone: (925) 750-6646
General Comments for this Test: SCC
Test Result Compliance:
Additional Comments When Verified:
Slump 23.5 inch

Test 3 of 7

DIME Test ID: 2021-07-08-20-3
Test Method: ASTM C231-17a: Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 07/09/2021
Date Tested: 07/08/2021
Submitted By Organization: Oldcastle Precast, Incorporated - Pleasanton
Organization Address: 1233 Quarry Lane, Suite 145,
Organization City: Pleasanton
Organization State: CA
Organization Zipcode: 94566
Organization Email: juan.maiz@oldcastle.com
Organization Phone: (925) 750-6646
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Air content 2.8 %

Test 4 of 7

DIME Test ID: 2021-07-08-20-4
Test Method: ASTM C138-17a: Standard Test Method for Density (Unit Weight), Yield, and Air Content (Gravimetric) of Concrete
Verified Date: 07/09/2021
Date Tested: 07/08/2021
Submitted By Organization: Oldcastle Precast, Incorporated - Pleasanton
Organization Address: 1233 Quarry Lane, Suite 145,
Organization City: Pleasanton
Organization State: CA
Organization Zipcode: 94566
Organization Email: juan.maiz@oldcastle.com
Organization Phone: (925) 750-6646
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Identification of concrete represented by the sample Mix No. 55
Volume of the measure 0.25 ft^3
Density of concrete 146.6 lb/ft^3
Yield of concrete 2.8 yd^3
Relative yield of the batch 1
Cement content 474 lb/yd^3
Air content 2.5 %

Test 5 of 7

DIME Test ID: 2021-07-08-20-5
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 07/09/2021
Date Tested: 07/09/2021
Submitted By Organization: Oldcastle Precast, Incorporated - Pleasanton
Organization Address: 1233 Quarry Lane, Suite 145,
Organization City: Pleasanton
Organization State: CA
Organization Zipcode: 94566
Organization Email: juan.maiz@oldcastle.com
Organization Phone: (925) 750-6646
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Average diameter of cylinder 1 5.99 in
Average diameter of cylinder 2 5.99 in
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Cross sectional area of cylinder 1 28.18 in^2
Cross sectional area of cylinder 2 28.18 in^2
Compressive strength (to nearest 10 psi) 3690 psi
Maximum load on cylinder 1 99850 lb
Maximum load on cylinder 2 107880 lb
Type of fracture pattern of cylinder 1 5
Type of fracture pattern of cylinder 2 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 1 days
Age of specimen in hours 19 hours

Test 6 of 7

DIME Test ID: 2021-07-08-20-6
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 07/15/2021
Date Tested: 07/15/2021
Submitted By Organization: Oldcastle Precast, Incorporated - Pleasanton
Organization Address: 1233 Quarry Lane, Suite 145,
Organization City: Pleasanton
Organization State: CA
Organization Zipcode: 94566
Organization Email: juan.maiz@oldcastle.com
Organization Phone: (925) 750-6646
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Average diameter of cylinder 1 5.99 in
Average diameter of cylinder 2 6.00 in
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Cross sectional area of cylinder 1 28.18 in^2
Cross sectional area of cylinder 2 28.27 in^2
Compressive strength (to nearest 10 psi) 6470 psi
Maximum load on cylinder 1 175740 lb
Maximum load on cylinder 2 189340 lb
Type of fracture pattern of cylinder 1 5
Type of fracture pattern of cylinder 2 4
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days
Age of specimen in hours 0 hours

Test 7 of 7

DIME Test ID: 2021-07-08-20-7
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 08/09/2021
Date Tested: 08/05/2021
Submitted By Organization: Oldcastle Precast, Incorporated - Pleasanton
Organization Address: 1233 Quarry Lane, Suite 145,
Organization City: Pleasanton
Organization State: CA
Organization Zipcode: 94566
Organization Email: juan.maiz@oldcastle.com
Organization Phone: (925) 750-6646
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Average diameter of cylinder 1 5.99 in
Average diameter of cylinder 2 5.99 in
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 3 5.99 in
Cross sectional area of cylinder 1 28.18 in^2
Cross sectional area of cylinder 2 28.18 in^2
Cross sectional area of cylinder 3 28.18 in^2
Compressive strength (to nearest 10 psi) 8130 psi
Maximum load on cylinder 1 230540 lb
Maximum load on cylinder 2 225620 lb
Maximum load on cylinder 3 230960 lb
Type of fracture pattern of cylinder 1 4
Type of fracture pattern of cylinder 2 4
Type of fracture pattern of cylinder 3 4
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days
Age of specimen in hours 0 hours