Print Report | Back to Test Summary

Testing Report for 2021-06-22-11-1

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 043G4424
EFIS: 0412000042
Project ID: 210037
QA Service Level: 1
DIST-CO-RTE-PM: 04-SF-80-R5.6/7.6
Work Description: WEST SPAN DAMPER BRACKET A325 BOLT TESTING
Location Description: SFOBB WEST SPAN
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Tom Larwin
Structure Rep.: Sergio Gomez

Sample Information

DIME Sample ID: 2021-06-22-11
TL Number from the TL Form: C725808
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (916) 227-7253
Type of Sample: Quality Assurance
Type of Material: SMTL TM3 - Fastener Assembly
Sample Taken Date: 6/22/2021
Date that the sample was received by the laboratory/organization performing the testing: 6/23/2021
The quantity of what the sample constitutes: 7
A brief description of the sample: A325 Bolt Assembly
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Bay Bolt

Material Information

Rocap Number(s):
Heat Number(s): NF14201810 100895271 163050
Nut Mfg. Lot Number(s): 426330A
Washer Mfg. Lot Number(s): 141843
Bolt Specification: A325
Bolt Length(s): 4.75"
Nut Specification: A563
Washer Specification: F436
Finish: HDG
Diameter/Size: 1"
Bolt Mfg. Lot Number: 347766A
Rocap Test Requirement(s):
Lubricant Requirements(s):

Test Information

DIME Test ID: 2021-06-22-11-1
Test Method: ASTM F606-14a: Standard Test Methods for Determining the Mechanical Properties of Externally and Internally Threaded Fasteners, Washers, Direct Tension Indicators, and Rivets (Proof Load with Wedge)
Date Tested: 6/24/2021
Verified Date: 6/29/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test: A325 Bolt
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Number of Bolt Samples: 1
Sample Bolt Mfg. Lot Number Size (in) Peak Load (lbf) Peak Load (kN) Wedge Angle (deg) Comments Tested By
1 347766A 1.0000 87739 390.28 10.00 A325 Bolt bewing
UTM: 450kip
Temperature: no data