Print Report | Back to Sample Detail

Sample Record for 2021-06-07-3

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 215075 DEA: 060Q9104 EFIS: 0614000005 QA Service Level: 1
DIST-CO-RTE-PM: 06-TUL-99-19.2/19.8
Work Description: BRIDGE DECK AND OUTSIDE GIRDER REPLACEMENT.
Location Description: TULARE COUNTY NEAR TIPTON FROM 0.3 MILE SOUTH TO 0.3 MILE NORTH OF AVENUE 152 OVERCROSSING
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 2716 Granite Court, Fresno, CA 93706
Resident Engineer: Javier Huerta Structure Rep.: Peter Moua

Sample Information

DIME Sample ID: 2021-06-07-3
TL Number from the TL Form:
Sample Submitted By Organization: Con-Fab California, LLC
Sample Organization Contact: (661) 630-7162
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 06/07/2021
Date that the sample was received by the laboratory/organization performing the testing: 06/09/2021
The quantity of what the sample constitutes: One girder
A brief description of the sample: PCC 6"x12" test cylinder
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Con-Fab California LLC

Material Information

The concrete mix design number: SCCS980F
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 1295
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Casting Bed 1
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 4

DIME Test ID: 2021-06-07-3-1
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 06/09/2021
Date Tested: 06/08/2021
Submitted By Organization: Con-Fab California, LLC
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: trevorl@confabca.com
Organization Phone: (661) 630-3281
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Average diameter of cylinder 1 6.00 in
Average diameter of cylinder 2 6.00 in
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Cross sectional area of cylinder 1 28.27 in^2
Cross sectional area of cylinder 2 28.27 in^2
Compressive strength (to nearest 10 psi) 6490 psi
Maximum load on cylinder 1 6430 lb
Maximum load on cylinder 2 6542 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 0 days
Age of specimen in hours 15 hours

Test 2 of 4

DIME Test ID: 2021-06-07-3-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 06/09/2021
Date Tested: 06/07/2021
Submitted By Organization: Con-Fab California, LLC
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: trevorl@confabca.com
Organization Phone: (661) 630-3281
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Slump 26 inch

Test 3 of 4

DIME Test ID: 2021-06-07-3-3
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 06/09/2021
Date Tested: 06/07/2021
Submitted By Organization: Con-Fab California, LLC
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: trevorl@confabca.com
Organization Phone: (661) 630-3281
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Temperature 80 F

Test 4 of 4

DIME Test ID: 2021-06-07-3-4
Test Method: ASTM C138-17a: Standard Test Method for Density (Unit Weight), Yield, and Air Content (Gravimetric) of Concrete
Verified Date: 06/09/2021
Date Tested: 06/07/2021
Submitted By Organization: Con-Fab California, LLC
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: trevorl@confabca.com
Organization Phone: (661) 630-3281
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Identification of concrete represented by the sample Girder
Volume of the measure 0.25 ft^3
Density of concrete 153.948 lb/ft^3
Yield of concrete no data
Relative yield of the batch no data
Cement content no data
Air content 1.2 %