Project ID: 214395 DEA: 103A7204 EFIS: 1013000259
QA Service Level: 1
DIST-CO-RTE-PM: 10-MER-99-20.1/24.3
Work Description: PLACE CRCP AND HMA.
Location Description: MERCED COUNTY IN AND NEAR ATWATER FROM 0.4 MILE SOUTH OF BUHACH OVERCROSSING TO 0.8 MILE NORTH OF WEST ATWATER OVERHEAD
Contractor Name: Bay Cities Paving & Grading
Contractor Address: 1450 Civic Ct. BLDG B #400, Concord CA, 94520
Resident Engineer: Muhammad Rahman Structure Rep.: Karen Sampson
DIME Sample ID: 2021-03-05-19
TL Number from the TL Form: C037435
Sample Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Sample Organization Contact: (916) 227-7302
Type of Sample: Acceptance
Type of Material: Asphalt Binder
Sample Taken Date: 03/05/2021
Date that the sample was received by the laboratory/organization performing the testing: 04/02/2021
The quantity of what the sample constitutes: 1 of 2
A brief description of the sample: Asphalt
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Santa Fe Aggregate Winton
Performance Grade: PG 70-10
Modified: No
Lot number:
Sublot number:
Tank number:
Time of sample:
HMA Supplier:
Certified Asphalt Supplier: Marathon Petroleum Co. LP - Elk Grove CA
Multigrade:
Multigrade Type:
Asphalt Binder Mix Number:
DIME Test ID: 2021-03-05-19-1
Test Method: AASHTO T240-17: Standard Method of Test for Effect of Heat and Air on a Moving Film of Asphalt Binder (Rolling Thin-Film Oven Test)
Verified Date: 04/07/2021
Date Tested: 04/06/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: per 2018 standard specifications
Test Result Compliance: complies
Additional Comments When Verified:
Is mass change based on one or two containers?
|
Two
|
Any material loss from containers during heating process/testing?
|
No
|
Mass of empty container #1
|
167.523 grams
|
Mass of empty container #2
|
169.871 grams
|
Mass of container #1 before test (m1i)
|
203.171 grams
|
Mass of container #2 before test (m2i)
|
205.806 grams
|
Mass of container #1 after test (m1f)
|
203.063 grams
|
Mass of container #2 after test (m2f)
|
205.694 grams
|
Average mass change
|
-0.307 percent
|
DIME Test ID: 2021-03-05-19-2
Test Method: AASHTO T315-16: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 04/07/2021
Date Tested: 04/06/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Std Specs ORIG
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
Original binder
|
Test Plate Diameter
|
25 mm
|
Test Gap
|
1 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
12.00 %
|
Stress Amplitude
|
0.163 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
87.5 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
1.361 kPa
|
Test Temperature (Specimen 1)
|
70.0 C
|
Dynamic Shear, G*/sin(δ)
|
1.36 kPa
|
DIME Test ID: 2021-03-05-19-3
Test Method: AASHTO T315-16: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 04/07/2021
Date Tested: 04/06/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Std Specs RTFO
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
RTFO residue
|
Test Plate Diameter
|
25 mm
|
Test Gap
|
1 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
10.00 %
|
Stress Amplitude
|
0.337 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
84.4 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
3.374 kPa
|
Test Temperature (Specimen 1)
|
70.0 C
|
Dynamic Shear, G*/sin(δ)
|
3.39 kPa
|
DIME Test ID: 2021-03-05-19-4
Test Method: AASHTO T315-16: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 04/07/2021
Date Tested: 04/07/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Std. Specs. PAV
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
PAV residue
|
Test Plate Diameter
|
8 mm
|
Test Gap
|
2 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
1.00 %
|
Stress Amplitude
|
34.823 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
52.4 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
3481.893 kPa
|
Test Temperature (Specimen 1)
|
34.0 C
|
(G*) x sin(δ)=
|
2759 kPa
|
DIME Test ID: 2021-03-05-19-5
Test Method: AASHTO T313-19: Standard Method of Test for Determining the Flexural Creep Stiffness of Asphalt Binder Using the Bending Beam Rheometer (BBR)
Verified Date: 04/07/2021
Date Tested: 04/07/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specs
Test Result Compliance: complies
Additional Comments When Verified:
Minimum test bath temperature at 240 s
|
0.0 C
|
Maximum test bath temperature at 240 s
|
0.0 C
|
Time of test load application
|
no data HH:MM:SS
|
File name of test data
|
no data
|
Time beam in bath
|
no data
|
Time test started
|
no data HH:MM:SS
|
Flags issued by software during test
|
no data
|
Correlation coefficient (R²)
|
0
|
Regression coefficient a
|
no data
|
Regression coefficient b
|
no data
|
Regression coefficient c
|
no data
|
Load at time 0.0
|
0.0 mN
|
Deflection at time 0.0 s
|
0.000 µm
|
Load at time 0.5 s
|
0.0 mN
|
Deflection at time 0.5 s
|
0.000 µm
|
Load at 60.0 s
|
0.0 mN
|
Beam deflection 60.0 s
|
0.000 µm
|
Measured Stiffness Modulus 60.0 s
|
67.500 mPa
|
Estimated Stiffness Modulus 60.0 s
|
67.600 mPa
|
Difference between stiffness moduli 60.0 s
|
no data
|
Estimated m-value 60.0 s
|
0.418
|