Print Report | Back to Test Summary

Testing Report for 2021-03-01-13-2

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 044G8204
EFIS: 0413000049
Project ID: 213653
QA Service Level: 1
DIST-CO-RTE-PM: 04-MRN-101-10.6/10.8
Work Description: REPLACE SAN RAFAEL HARBOR BRIDGE (ABC)
Location Description: MARIN COUTY, IN SAN RAFAEL, FROM ROUTE 101 NORTHBOUND OFF-RAMP TO 2ND STREET
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Dawit Habteselassie
Structure Rep.: Long N Ly

Sample Information

DIME Sample ID: 2021-03-01-13
TL Number from the TL Form:
Sample Submitted By Organization: Caltrans Vallejo Field Laboratory
Sample Organization Contact: (510) 774-6009
Type of Sample: Quality Assurance
Type of Material: SMTL TM3 - Fastener Assembly
Sample Taken Date: 3/1/2021
Date that the sample was received by the laboratory/organization performing the testing: 3/11/2021
The quantity of what the sample constitutes: 45 assemblies
A brief description of the sample: 1” x 4” bolt with washer and nut
From where was the sample collected: Fabricator
Laboratory sample identification: AB548A
Structure unique identifier:
Structure name: Temporary Modular Bridge
The fabricator/manufacturer/facility name: Acrow Bridge

Material Information

Rocap Number(s): TBD
Heat Number(s): TBD
Nut Mfg. Lot Number(s):
Washer Mfg. Lot Number(s):
Bolt Specification: ASTM F3125 Grade A325
Bolt Length(s): 4”
Nut Specification: ASTM A563 Grade DH
Washer Specification: ASTM F436
Finish: HDG ASTM A153
Diameter/Size: 1"
Bolt Mfg. Lot Number:
Rocap Test Requirement(s):
Lubricant Requirements(s):

Test Information

DIME Test ID: 2021-03-01-13-2
Test Method: ASTM F606-14a: Standard Test Methods for Determining the Mechanical Properties of Externally and Internally Threaded Fasteners, Washers, Direct Tension Indicators, and Rivets (Proof Load with Wedge)
Date Tested: 3/17/2021
Verified Date: 3/25/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test: A325
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Number of Bolt Samples: 1
Sample Bolt Mfg. Lot Number Size (in) Peak Load (lbf) Peak Load (kN) Wedge Angle (deg) Comments Tested By
1A AB548A 1.0000 89792 399.41 10.00 A325 fsaylor
UTM: 450kip
Temperature: no data