Print Report | Back to Test Summary

Testing Report for 2020-10-23-10-3

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 041J5694
EFIS: 0419000313
Project ID: 214601
QA Service Level: 1
DIST-CO-RTE-PM: 04-SM-101-0.0/21.8
Work Description: Barrier modifications, overhead signs, freeway lighting and electronic toll system components
Location Description: SANTA CLARA AND SAN MATEO COUNTIES FROM 0.3 MILE NORTH OF SAN ANTONIO ROAD TO 0.3 MILE SOUTH OF GRAND AVENUE INTERCHANGE
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Douglas Inori
Structure Rep.: Tyler Pinell

Sample Information

DIME Sample ID: 2020-10-23-10
TL Number from the TL Form:
Sample Submitted By Organization: Pro-Cast Products Inc.
Sample Organization Contact: (909) 793-7602
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 10/23/2020
Date that the sample was received by the laboratory/organization performing the testing: 10/26/2020
The quantity of what the sample constitutes: 53
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Procast

Material Information

The concrete mix design number: RRM14062
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 5749752
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Concrete from wheelbarrow
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Information

DIME Test ID: 2020-10-23-10-3
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Date Tested: 11/24/2020
Verified Date: 12/11/2020
Submitted By Organization: Pro-Cast Products Inc.
Organization Address: 27417 E. Third St., PO Box 602,
Organization City: Highland
Organization State: CA
Organization Zipcode: 92346
Organization Email: chad@procast.us
Organization Phone: (909) 793-7602
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Average diameter of cylinder 1: 6.00 in
Average diameter of cylinder 2: 6.00 in
Capped in accordance with?: ASTM C617/CTM521
Cross sectional area of cylinder 1: 28.27 in^2
Cross sectional area of cylinder 2: 28.27 in^2
Compressive strength (to nearest 10 psi): 6170 psi
Maximum load on cylinder 1: 176120 lb
Maximum load on cylinder 2: 172310 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: no data
Correction factor for cylinder 2: no data
Age of specimen: 28 days
Age of specimen in hours: no data