Project Information

Project ID: 213406 DEA: 030F2504 EFIS: 0300000075 QA Service Level: 1
DIST-CO-RTE-PM: 03-YOL,SAC-80-R11.1/R11.7,M0.0/M0.5
Work Description: SAC RIVER BOH (BRYTE BEND)
Location Description: SACRAMENTO AND YOLO COUNTIES IN WEST SACRAMENTO AND SACRAMENTO FROM 0.1 MILE WEST OF REED AVENUE UNDERCROSSING TO 0.1 MILE EAST OF SACRAMENTO RIVER BRIDGE AND OVERHEAD
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Ephrem Teweldeberhan Structure Rep.: Bullard, Brent

Sample Information

DIME Sample ID: 2021-02-10-1
TL Number from the TL Form:
Sample Submitted By Organization: CT QASI - Sacramento Field Laboratory
Sample Organization Contact: (916) 227-7263
Type of Sample: Quality Assurance
Type of Material: SMTL TM3 - Fastener Assembly
Sample Taken Date: 02/10/2021
Date that the sample was received by the laboratory/organization performing the testing: 02/12/2021
The quantity of what the sample constitutes: 5,563 bolts
A brief description of the sample: ASTM A325 Bolts
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CK Johnson

Material Information

Rocap Number(s): 443696A
Heat Number(s): 100205135
Nut Mfg. Lot Number(s): N/A
Washer Mfg. Lot Number(s): N/A
Bolt Specification: ASTM A325
Bolt Length(s): 2-1/4"
Nut Specification: N/A
Washer Specification: N/A
Finish: ASTM F2329 HDG
Diameter/Size: 5/8"
Bolt Mfg. Lot Number: 443696A
Rocap Test Requirement(s): YES
Lubricant Requirements(s):

Test Information

DIME Test ID: 2021-02-10-1-1
Test Method: ASTM F606-14a: Standard Test Methods for Determining the Mechanical Properties of Externally and Internally Threaded Fasteners, Washers, Direct Tension Indicators, and Rivets (Proof Load with Wedge)
Verified Date: 03/02/2021
Date Tested: 02/18/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test: A325 Bolt
Additional Comments When Verified:

Submitted Test Results

Sample No. 1E
Rocap Number no data
Heat Number(s) no data
Mfg. Lot Number 443696A
Finish Coating ASTM F2329 - Hot Dip
Product Markings A325 N USA
Size .625 in
Bolt Length 2.25 in
Gage Type Pass