Print Report | Back to Sample Detail

Sample Record for 2020-01-29-11

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 213764 DEA: 080F0304 EFIS: 0800020358 QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-60-R0.7/R3.0
Work Description: REMOVE AND REPLACE THREE OVERCROSSING BRIDGES ON ROUTE 60
Location Description: IN SAN BERNARDINO COUNTY IN AND NEAR CHINO AT VARIOUS LOCATIONS FROM O.1 MILE WEST OF PIPELINE AVENUE OVERCROSSING TO 0.1 MILE EAST OF BENSON AVENUE OVERCROSSING
Contractor Name: SEMA CONSTRUCTION, INC.
Contractor Address: 42690 Rio Nedo, Suite G, Temecula, CA 92590
Resident Engineer: Joseph Lopez Structure Rep.: Rodrigo Santa Cruz

Sample Information

DIME Sample ID: 2020-01-29-11
TL Number from the TL Form: L133-015-20
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 01/29/2020
Date that the sample was received by the laboratory/organization performing the testing: 01/31/2020
The quantity of what the sample constitutes: 4 coupled bars
A brief description of the sample: Lot 2 #6 Rebar Coupled bars
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Integrity Rebar Placers

Material Information

Production or Authorization Testing: Production Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: CMC
Coupler Manufacturer: BarSplice
Intermediate Assembler or Fabricator:
Rebar Size: 6
Coupler Model: 6DBZA
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): 8249
Rebar Heat Number(s): 4088284
Rebar Size 2 : 6
Coupler Unique ID:

Test Results

Test 1 of 3

DIME Test ID: 2020-01-29-11-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 02/03/2020
Date Tested: 01/31/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
SampleMfg. Lot Number(s)SizeArea (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
126/19mm0.4443635.3699171Service Splicebewing
UTM 400kip
Temperature 72 f

Test 2 of 3

DIME Test ID: 2020-01-29-11-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 02/03/2020
Date Tested: 01/31/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
SampleMfg. Lot Number(s)SizeArea (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
226/19mm0.4443721.7299368Service Splicebewing
UTM 400kip
Temperature 72 f

Test 3 of 3

DIME Test ID: 2020-01-29-11-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 02/03/2020
Date Tested: 01/31/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
SampleMfg. Lot Number(s)SizeArea (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
326/19mm0.4439399.2389544Service Splicebewing
UTM 400kip
Temperature 72 f