Sample Record for 2024-07-11-109

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 214698 DEA: 120N8904 EFIS: 1214000130 QA Service Level: 1
DIST-CO-RTE-PM: 12-ORA-133-8.3/M9.3
Work Description: CONSTRUCT AUXILIARY LANE.
Location Description: ORANGE COUNTY IN IRVINE FROM ROUTE 133/405 SEPARATION TO IRVINE CENTER DRIVE OVERCROSSING
Contractor Name: SECURITY PAVING COMPANY, INC.
Contractor Address: 3200 Park Center Drive, Suite #200, Costa Mesa, CA 92626
Resident Engineer: Arezo Ghiam Structure Rep.: Melissa Quintana

Sample Information

DIME Sample ID: 2024-07-11-109
TL Number from the TL Form:
Sample Submitted By Organization: CT D12 - Huntington Beach Field Laboratory
Sample Organization Contact: 9492798846
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 07/11/2024
Date that the sample was received by the laboratory/organization performing the testing: 07/12/2024
The quantity of what the sample constitutes: 3
A brief description of the sample: 4x8 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 24-0311
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: NATIONAL

Material Information

The concrete mix design number: S72C447T14
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 419895
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Concrete from wheelbarrow
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 1

DIME Test ID: 2024-07-11-109-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 08/19/2024
Date Tested: 08/08/2024
Submitted By Organization: CT D12 - Huntington Beach Field Laboratory
Organization Address: 19601 Beach Boulevard,
Organization City: Huntington Beach
Organization State: CA
Organization Zipcode: 92648
Organization Email: frank.mai@dot.ca.gov
Organization Phone: (949) 279-8846
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 3.98 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.44 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 5320 psi
Maximum load on cylinder 1 67910 lb
Maximum load on cylinder 2 64460 lb
Maximum load on cylinder 3 67580 lb
Compressive strength of cylinder 1 5402.5 psi
Type of fracture pattern of cylinder 1 3
Compressive strength of cylinder 2 5181.7 psi
Compressive strength of cylinder 3 5376.3 psi
Type of fracture pattern of cylinder 2 3
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days
Age of specimen in hours no data0 hours