Print Report | Back to Sample Detail

Sample Record for 2024-05-20-92

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 214698 DEA: 120N8904 EFIS: 1214000130 QA Service Level: 1
DIST-CO-RTE-PM: 12-ORA-133-8.3/M9.3
Work Description: CONSTRUCT AUXILIARY LANE.
Location Description: ORANGE COUNTY IN IRVINE FROM ROUTE 133/405 SEPARATION TO IRVINE CENTER DRIVE OVERCROSSING
Contractor Name: SECURITY PAVING COMPANY, INC.
Contractor Address: 3200 Park Center Drive, Suite #200, Costa Mesa, CA 92626
Resident Engineer: Arezo Ghiam Structure Rep.: Melissa Quintana

Sample Information

DIME Sample ID: 2024-05-20-92
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 05/20/2024
Date that the sample was received by the laboratory/organization performing the testing: 05/30/2024
The quantity of what the sample constitutes: 106
A brief description of the sample: zap screw lock type 2
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Jobsite

Material Information

Production or Authorization Testing: Production Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Cascade
Coupler Manufacturer: BarSplice
Intermediate Assembler or Fabricator:
Rebar Size: #8
Coupler Model: Zap Screwlok Coupler Type 2
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): A160343
Rebar Heat Number(s): 447422
Rebar Size 2 :
Coupler Unique ID: SL-17-03

Test Results

Test 1 of 4

DIME Test ID: 2024-05-20-92-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 05/30/2024
Date Tested: 05/29/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested 1
SampleNumber of CyclesSizeMfg. Lot Number(s)Slip (inch)Area (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
1No. 8/25mm2-0.00440.797333792832Service Spliceaauvinen
UTM 400kip
Temperature 72.00 f
Halo ID Small

Test 2 of 4

DIME Test ID: 2024-05-20-92-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 05/30/2024
Date Tested: 05/29/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested 1
SampleNumber of CyclesSizeMfg. Lot Number(s)Slip (inch)Area (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
2No. 8/25mm200.796104577272Service Spliceaauvinen
UTM 400kip
Temperature 72.00 f
Halo ID

Test 3 of 4

DIME Test ID: 2024-05-20-92-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 05/30/2024
Date Tested: 05/29/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested 1
SampleNumber of CyclesSizeMfg. Lot Number(s)Slip (inch)Area (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
3No. 8/25mm200.796992888517Service Spliceaauvinen
UTM 400kip
Temperature 72.00 f
Halo ID

Test 4 of 4

DIME Test ID: 2024-05-20-92-4
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 05/30/2024
Date Tested: 05/29/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested 1
SampleNumber of CyclesSizeMfg. Lot Number(s)Slip (inch)Area (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
4No. 8/25mm200.797071389510Service Spliceaauvinen
UTM 400kip
Temperature 72.00 f
Halo ID