Sample Record for 2016-09-09-6
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 210696 DEA: 080M2804 EFIS: 0800000472
QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-15-171.8/173.8
Work Description: BRIDGE REPLACEMENT AND WIDEN, CONC AND HMA PVMT, COLD PLANE AC PVMT.
Location Description: In SBD County
Contractor Name: M.C.M. CONSTRUCTION, INC. - Dan Shaw
Contractor Address: P.O. Box 620, North Highlands, CA 95660
Resident Engineer: John Santos Structure Rep.: Faisal Zahlout
Sample Information
DIME Sample ID: 2016-09-09-6
TL Number from the TL Form: 942-05
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 09/09/2016
Date that the sample was received by the laboratory/organization performing the testing: 09/09/2016
The quantity of what the sample constitutes: 8
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 942-05
Structure unique identifier: Unknown
Structure name: Unknown
The fabricator/manufacturer/facility name: Jobsite
Material Information
The concrete mix design number: P40F023
The truck number from where the sample was collected: A031
The batch plant ticket number from where the sample was collected: S485389
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: Dischard fron concrete truck into wheelbarrow.
Where the material sample would have been placed if not sampled: jobsite
From Lot No.: Unknown
Bag Lot No.: Unknown
Test Results
Test 1 of 3
DIME Test ID: 2016-09-09-6-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521 Cured in accordance with ASTM C511
Verified Date: 09/16/2016
Date Tested: 09/16/2016
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.18 in^2
|
Cross sectional area of cylinder 2
|
28.18 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
4240 psi
|
Average diameter of cylinder 1
|
5.99 in
|
Average diameter of cylinder 2
|
5.99 in
|
Compressive strength of cylinder 1
|
4209.7 psi
|
Compressive strength of cylinder 2
|
4276.1 psi
|
Maximum load on cylinder 1
|
118630 lb
|
Maximum load on cylinder 2
|
120500 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
7 days
|
Test 2 of 3
DIME Test ID: 2016-09-09-6-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521 Cured in accordance with ASTM C511
Verified Date: 10/03/2016
Date Tested: 09/30/2016
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.18 in^2
|
Cross sectional area of cylinder 2
|
28.18 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
5510 psi
|
Average diameter of cylinder 1
|
5.99 in
|
Average diameter of cylinder 2
|
5.99 in
|
Compressive strength of cylinder 1
|
5509.2 psi
|
Compressive strength of cylinder 2
|
5509.9 psi
|
Maximum load on cylinder 1
|
155250 lb
|
Maximum load on cylinder 2
|
155270 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
21 days
|
Test 3 of 3
DIME Test ID: 2016-09-09-6-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521 Cured in accordance with ASTM C511
Verified Date: 10/07/2016
Date Tested: 10/07/2016
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.18 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
5770 psi
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
5.99 in
|
Compressive strength of cylinder 1
|
5736.1 psi
|
Compressive strength of cylinder 2
|
5802.3 psi
|
Maximum load on cylinder 1
|
162160 lb
|
Maximum load on cylinder 2
|
163510 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
28 days
|
Tests Assigned to this Sample
DIME Test ID | Test Method | Assigned Date | Test Date | Assigned By | Assigned Lab | Test Comments | Assigned To |
2016-09-09-6-4 | ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens | 09/15/2016 | 10/21/2016 | Friday Ofoegbu | CT D08 - Fontana Southern Regional Laboratory | HOLD | |
6133