Print Report | Back to Sample Detail

Sample Record for 2024-04-19-20

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 215677 DEA: 044G0804 EFIS: 0412000332 COOP: 042676 QA Service Level: 1
DIST-CO-RTE-PM: 04-SOL-80-R10.4/30.2
Work Description: Highway widening, overhead signs, and electronic toll system.
Location Description: In Solano County in Fairfield and Vacaville from 1.0 mile west of Red Top Road Undercrossing to 0.4 mile east of Leisure Town Road Overcrossing.
Contractor Name: O.C. JONES & SONS, INC.
Contractor Address: 1520 Fourth Street, Berkeley, CA 94710
Resident Engineer: Justen Tatum Structure Rep.: Mohan Ayadurai

Sample Information

DIME Sample ID: 2024-04-19-20
TL Number from the TL Form:
Sample Submitted By Organization: Rinker Materials
Sample Organization Contact: (916) 381-3910
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 04/19/2024
Date that the sample was received by the laboratory/organization performing the testing: 04/19/2024
The quantity of what the sample constitutes: Day's Production
A brief description of the sample: 4x8 concrete cylinders
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Rinker Materials

Material Information

The concrete mix design number: mix 5
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 2-12241
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Besser Hopper
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 4

DIME Test ID: 2024-04-19-20-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 04/22/2024
Date Tested: 04/19/2024
Submitted By Organization: Rinker Materials
Organization Address: 7020 Tokay Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95828
Organization Email: Edgar.Benitez@Rinkerpipe.com
Organization Phone: (209) 401-6972
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Temperature 74 F

Test 2 of 4

DIME Test ID: 2024-04-19-20-2
Test Method: CTM TEMP1-16: Test Method for Monitoring Precast Concrete Curing Temperature (Curing temperature)
Verified Date: 04/22/2024
Date Tested: 04/19/2024
Submitted By Organization: Rinker Materials
Organization Address: 7020 Tokay Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95828
Organization Email: Edgar.Benitez@Rinkerpipe.com
Organization Phone: (209) 401-6972
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Precast Maximum Curing Temperature 87 °F

Test 3 of 4

DIME Test ID: 2024-04-19-20-3
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 04/22/2024
Date Tested: 04/20/2024
Submitted By Organization: Rinker Materials
Organization Address: 7020 Tokay Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95828
Organization Email: Edgar.Benitez@Rinkerpipe.com
Organization Phone: (209) 401-6972
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Compressive strength (to nearest 10 psi) 2400 psi
Maximum load on cylinder 1 30780 lb
Maximum load on cylinder 2 29520 lb
Type of fracture pattern of cylinder 1 5
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 1 days
Age of specimen in hours 0 hours

Test 4 of 4

DIME Test ID: 2024-04-19-20-4
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 05/01/2024
Date Tested: 04/26/2024
Submitted By Organization: Rinker Materials
Organization Address: 7020 Tokay Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95828
Organization Email: Edgar.Benitez@Rinkerpipe.com
Organization Phone: (209) 401-6972
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Compressive strength (to nearest 10 psi) 6590 psi
Maximum load on cylinder 1 84525 lb
Maximum load on cylinder 2 81260 lb
Type of fracture pattern of cylinder 1 2
Type of fracture pattern of cylinder 2 4
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days
Age of specimen in hours 0 hours