DIME Sample ID: 2016-08-24-15
TL Number from the TL Form: C970415
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Recertification
Type of Material: SMTL TM5 - Welded Hoops
Sample Taken Date: 08/24/2016
Date that the sample was received by the laboratory/organization performing the testing: 08/30/2016
The quantity of what the sample constitutes: 16
A brief description of the sample: Flash Welded Rebar Hoops
From where was the sample collected: Fabricator
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: RKR Steel Welding
Production or Authorization Testing: Authorization Testing
Service or Ultimate: Ultimate
Rebar Heat Number(s): 082816
Hoop Manufacturer Lot Number(s): NA
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Size: 7
Diameter of Hoop: 29, 60
Epoxy Coated: No
Epoxy Coating Color: NA
Rebar Manufacturer: Cascade
Welding Company: RKR Steel Welding
Coating Standards: Uncoated
Weld Type: Flash Welded
DIME Test ID: 2016-08-24-15-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/07/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Cycle-1 Small | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 58122 | 96870 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/07/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Cycle-2 Small | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 57737 | 96228 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/08/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Cycle-3 Small | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 57687 | 96145 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-4
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/08/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Cycle-4 Small | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 57584 | 95973 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-5
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/08/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Break-1 Small | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 57648 | 96080 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-6
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/08/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Break-2 Small | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 57815 | 96358 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-7
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/08/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Break-3 Small | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 58335 | 97225 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-8
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/08/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Break-4 Small | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 58042 | 96737 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-9
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/08/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Cycle-1 Large | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 58730 | 97883 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-10
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/08/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Cycle-2 Large | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 58643 | 97738 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-11
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/08/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Cycle-3 Large | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 58435 | 97392 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-12
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/08/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Cycle-4 Large | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 58613 | 97688 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-13
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/08/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Break-1 Large | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 58583 | 97638 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-14
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/08/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Break-2 Large | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 58203 | 97005 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-15
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/08/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Break-3 Large | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 58343 | 97238 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2016-08-24-15-16
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical)
Verified Date: 10/04/2016
Date Tested: 09/08/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: NECKING OK
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | Break-4 Large | 100 | #7/22mm | Janda Resistance F4-300 | 0.6 | 58148 | 96913 | NECKING OK | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|