Project ID: 993387 DEA: 07323404 EFIS: 0716000064
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-5-R59.5/R67.9
Work Description: PLACE CULVERT, REPLACE DRAINAGE SYSTEM, RECONST ROADWAY & EMBANKMENT.
Location Description: LOS ANGELES COUNTY AT VARIOUS LOCATIONS FROM LAKE HUGHES ROAD UNDERCROSSING TO 1.9 MILES NORTH OF TEMPLIN HIGHWAY UNDERCROSSING
Contractor Name: SECURITY PAVING COMPANY INC
Contractor Address: 13170 TELEFAIR AVE, SYLMAR, CA 91342
Resident Engineer: Oscar Osorio Structure Rep.: Chanh Tong
DIME Sample ID: 2023-11-17-92
TL Number from the TL Form:
Sample Submitted By Organization: Alta Vista Solutions - Whittier
Sample Organization Contact: (510) 542-9827
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 11/17/2023
Date that the sample was received by the laboratory/organization performing the testing: 11/17/2023
The quantity of what the sample constitutes: 10 cubic yards
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 23-2053
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: N/A
The concrete mix design number: G3-21-CTS-220
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 11
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: wheelbarrow
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-11-17-92-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 02/27/2024
Date Tested: 11/24/2023
Submitted By Organization: Alta Vista Solutions - Whittier
Organization Address: 12409 Slauson Avenue, Suite I,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90606
Organization Email: nicholas.hoffmann@oneatlas.com
Organization Phone: (510) 542-9827
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
Average diameter of cylinder 1
|
5.96 in
|
Average diameter of cylinder 2
|
5.96 in
|
Cross sectional area of cylinder 1
|
27.9 in^2
|
Cross sectional area of cylinder 2
|
27.9 in^2
|
Compressive strength (to nearest 10 psi)
|
4630 psi
|
Maximum load on cylinder 1
|
128111 lb
|
Maximum load on cylinder 2
|
130213 lb
|
Compressive strength of cylinder 1
|
4,591.8 psi
|
Type of fracture pattern of cylinder 1
|
2
|
Compressive strength of cylinder 2
|
4,667.1 psi
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1.00
|
Correction factor for cylinder 2
|
1.00
|
Age of specimen
|
7 days
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2023-11-17-92-2
Test Method: CTM 557-June 2020: Method of Test for Temperature of Freshly Mixed Hydraulic Cement Concrete
Verified Date: 02/27/2024
Date Tested: 11/17/2023
Submitted By Organization: Alta Vista Solutions - Whittier
Organization Address: 12409 Slauson Avenue, Suite I,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90606
Organization Email: nicholas.hoffmann@oneatlas.com
Organization Phone: (510) 542-9827
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified: