Project ID: 994629 DEA: 020J5404 EFIS: 0219000134
QA Service Level: 1
DIST-CO-RTE-PM: 02---
Work Description:
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown
DIME Sample ID: 2023-08-10-90
TL Number from the TL Form: 897775
Sample Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Sample Organization Contact: (530) 225-3194
Type of Sample: Preliminary
Type of Material: Soil
Sample Taken Date: 08/10/2023
Date that the sample was received by the laboratory/organization performing the testing: 08/11/2023
The quantity of what the sample constitutes: Culvert Recommendation C-2
A brief description of the sample: Soil for culvert recommendation
From where was the sample collected: Job Site
Laboratory sample identification: D79317
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: In Situ
The fabricator's/manufacturer's product name for the sample:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: 02-SIS-3-50.17, 25 ft. Rt of CL, 0.5 ft. below OG
Where the material sample would have been placed if not sampled:
DIME Test ID: 2023-08-10-90-1
Test Method: CTM 643-April 2020: Method for Test for Laboratory Resistivity and pH for Soil and Water
Verified Date: 01/29/2024
Date Tested: 08/16/2023
Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Organization Address: 1657 Riverside Drive,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: ward.jenkins@dot.ca.gov
Organization Phone: 530-225-3194
General Comments for this Test: pH=6.51,
ρ=1874Ω∙cm
Test Result Compliance: not applicable
Additional Comments When Verified:
Minimum soil resistance corrected to 15.5
|
1874.25 Ohm-cm
|
Minimum soil resistivity at 15.5
|
1874 Ohm-cm
|
Minimum soil resistance of the lab measurement
|
1700 Ohms
|
Soil sample temperature
|
19.6 C
|
pH of soil
|
6.51
|