Print Report | Back to Sample Detail

Sample Record for 2024-01-26-14

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 994671 DEA: 010H8004 EFIS: 0118000110 QA Service Level: 1
DIST-CO-RTE-PM: 01-HUM-254-4.3/4.7
Work Description: Project Name: Myers Flat Permanent Restoration
Location Description: Bridge No. 04E0041
Contractor Name: McCullough Construction Inc.
Contractor Address: 57 Alder Grove Road, Arcata, CA 95521
Resident Engineer: Brian Apple Structure Rep.: Alexander Mattson

Sample Information

DIME Sample ID: 2024-01-26-14
TL Number from the TL Form:
Sample Submitted By Organization: CT D01 - District 1 Materials Laboratory
Sample Organization Contact: (707) 496-0974
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 01/26/2024
Date that the sample was received by the laboratory/organization performing the testing: 01/29/2024
The quantity of what the sample constitutes: Unknown Quantity
A brief description of the sample: 4x8 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: C0263
Structure unique identifier: 04-E0041
Structure name:
The fabricator/manufacturer/facility name: Eureka Ready mix

Material Information

The concrete mix design number: Unknown
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: not given
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Mixer truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 3

DIME Test ID: 2024-01-26-14-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 02/02/2024
Date Tested: 02/02/2024
Submitted By Organization: CT D01 - District 1 Materials Laboratory
Organization Address: 1726 Albee Street,
Organization City: Eureka
Organization State: CA
Organization Zipcode: 95501
Organization Email: leif.ayres@dot.ca.gov
Organization Phone: (707) 496-0974
General Comments for this Test: 7 Day Break 2/2/24
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 2970 psi
Maximum load on cylinder 1 38110 lb
Maximum load on cylinder 2 36970 lb
Maximum load on cylinder 3 36730 lb
Type of fracture pattern of cylinder 1 5
Type of fracture pattern of cylinder 2 5
Type of fracture pattern of cylinder 3 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 7 days
Age of specimen in hours 0 hours

Test 2 of 3

DIME Test ID: 2024-01-26-14-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 02/05/2024
Date Tested: 02/05/2024
Submitted By Organization: CT D01 - District 1 Materials Laboratory
Organization Address: 1726 Albee Street,
Organization City: Eureka
Organization State: CA
Organization Zipcode: 95501
Organization Email: leif.ayres@dot.ca.gov
Organization Phone: (707) 496-0974
General Comments for this Test: 10 Day Break 2/5/24
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 3320 psi
Maximum load on cylinder 1 40110 lb
Maximum load on cylinder 2 42350 lb
Maximum load on cylinder 3 42650 lb
Compressive strength of cylinder 1 3190.9 psi
Type of fracture pattern of cylinder 1 5
Compressive strength of cylinder 2 3369.1 psi
Compressive strength of cylinder 3 3393 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 10 days
Age of specimen in hours 0 hours

Test 3 of 3

DIME Test ID: 2024-01-26-14-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 02/23/2024
Date Tested: 02/23/2024
Submitted By Organization: CT D01 - District 1 Materials Laboratory
Organization Address: 1726 Albee Street,
Organization City: Eureka
Organization State: CA
Organization Zipcode: 95501
Organization Email: leif.ayres@dot.ca.gov
Organization Phone: (707) 496-0974
General Comments for this Test: 28 Day Break 2/23/24
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.6 in^2
Cross sectional area of cylinder 2 12.6 in^2
Cross sectional area of cylinder 3 12.6 in^2
Compressive strength (to nearest 10 psi) 4770 psi
Maximum load on cylinder 1 61390 lb
Maximum load on cylinder 2 62310 lb
Maximum load on cylinder 3 56310 lb
Type of fracture pattern of cylinder 1 5
Type of fracture pattern of cylinder 2 5
Type of fracture pattern of cylinder 3 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days
Age of specimen in hours 0 hours