Sample Record for 2024-01-12-35
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 210409 DEA: 08432724 EFIS: 0800020178
QA Service Level: 2
DIST-CO-RTE-PM: 08-RIV-8-RIV-15-6.4/9.7
Work Description: Collector/distributor system, new on-ramps, bridges, RW, sound walls, drainage, signal and lighting, signage, freeway widening
Location Description: I-15 from Winchester Road to I-215 Junction in Temecula
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Mike Bergevin Structure Rep.: Arnel Vega
Sample Information
DIME Sample ID: 2024-01-12-35
TL Number from the TL Form:
Sample Submitted By Organization: Surecast West
Sample Organization Contact: (951) 491-9506
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 01/12/2024
Date that the sample was received by the laboratory/organization performing the testing: 01/22/2024
The quantity of what the sample constitutes: 10.00
A brief description of the sample: TYPE II/V
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CEMEX-REDLANDS
Material Information
The concrete mix design number: 1610974
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 31075680
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: SAMPLE FROM WHEELBARROW
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 1
DIME Test ID: 2024-01-12-35-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 01/26/2024
Date Tested: 01/22/2024
Submitted By Organization: Surecast West
Organization Address: 8203 Alabama Street,
Organization City: Redlands
Organization State: CA
Organization Zipcode: 92373
Organization Email: cody@surecastwest.com
Organization Phone: (951) 491-9506
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Average diameter of cylinder 1
|
4.00 in
|
Average diameter of cylinder 2
|
4.00 in
|
Average diameter of cylinder 3
|
4.00 in
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
Compressive strength (to nearest 10 psi)
|
5170 psi
|
Maximum load on cylinder 1
|
64890 lb
|
Maximum load on cylinder 2
|
65210 lb
|
Maximum load on cylinder 3
|
64820 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Type of fracture pattern of cylinder 3
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Correction factor for cylinder 3
|
1
|
Age of specimen
|
10 days
|
Age of specimen in hours
|
0 hours
|