Sample Record for 2023-12-19-6
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 994327 DEA: 081G4704 EFIS: 0816000001
QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-74-3.1/53.5
Work Description: STRUCTURAL CONC BR, CONC SLAB, HMA (TYPE A), ALT CRASH CUSHION SYSTEM.
Location Description: RIVERSIDE COUNTY NEAR LAKE ELSINORE AT MORRILL CANYON BRIDGE AND NEAR HEMET AT STRAWBERRY CREEK BRIDGE.
Contractor Name: BEADOR CONSTRUCTION COMPANY, INC.
Contractor Address: 26320 LESTER CIRCLE;, CORONA CA 92883
Resident Engineer: Mike A Bergevin Structure Rep.: Arnel Vega
Sample Information
DIME Sample ID: 2023-12-19-6
TL Number from the TL Form:
Sample Submitted By Organization: CT D08 - Corona-Stellar Structures Construction Field Office
Sample Organization Contact: 951-906-9897
Type of Sample: Acceptance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 12/19/2023
Date that the sample was received by the laboratory/organization performing the testing: 01/03/2024
The quantity of what the sample constitutes: 4
A brief description of the sample: #6 Lenton Form Saver Coupler
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier: 56-0180
Structure name: Strawberry Creek Bridge
The fabricator/manufacturer/facility name: nVent Lenton Form Savers
Material Information
Production or Authorization Testing: Authorization Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: CMC Steel Arizona
Coupler Manufacturer: nVent Lenton
Intermediate Assembler or Fabricator:
Rebar Size: #6
Coupler Model: Threaded Type (SA)
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): M0129
Rebar Heat Number(s): 4134981
Rebar Size 2 :
Coupler Unique ID: ST-17-05
Test Results
Test 1 of 3
DIME Test ID: 2023-12-19-6-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 1 | | No. 6/19mm | 1 | -0.0005 | 0.44 | 42422 | 96413 | Service Splice | aauvinen |
| |
UTM
|
400kip
|
Temperature
|
72.00 f
|
Halo ID
|
Small
|
Test 2 of 3
DIME Test ID: 2023-12-19-6-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 2 | | No. 6/19mm | 1 | 0 | 0.44 | 42420 | 96409 | Service Splice | aauvinen |
| |
UTM
|
400kip
|
Temperature
|
72.00 f
|
Halo ID
|
|
Test 3 of 3
DIME Test ID: 2023-12-19-6-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 3 | | No. 6/19mm | 1 | 0 | 0.44 | 42369 | 96294 | Service Splice | aauvinen |
| |
UTM
|
400kip
|
Temperature
|
72.00 f
|
Halo ID
|
|