Print Report | Back to Sample Detail

Sample Record for 2023-11-09-52

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 209820 DEA: 04297634 EFIS: 0415000040 COOP: 042548 QA Service Level: 1
DIST-CO-RTE-PM: 04-ALA-84,680-17.9/21
Work Description: ROUTE 84 WIDENING (4-LANE EXPRESSWAY) FROM I-680 TO PIGEON PASS, INCLUDING INTERSECTION, DRAINAGE IMPROVEMENTS AND UTILITY RELOCATION.
Location Description: ALAMEDA COUNTY IN AND NEAR SUNOL, PLEASANTON, AND LIVERMORE ON ROUTE 84 FROM 0.1 MILE EAST OF ROUTE 680 TO 0.1 MILE SOUTH OF RUBY HILL DRIVE AND ON ROUTE 680 FROM 1.2 MILES SOUTH TO 1.8 MILES NORTH OF ROUTE 84
Contractor Name: Bay Cities Paving & Grading
Contractor Address: 1450 Civic Ct. BLDG B #400, Concord CA, 94520
Resident Engineer: Paramjit Pandher Structure Rep.: Ehab Wahed

Sample Information

DIME Sample ID: 2023-11-09-52
TL Number from the TL Form: 031627
Sample Submitted By Organization: CT SC - 3674 - Livermore
Sample Organization Contact: (510) 393-1493
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 11/09/2023
Date that the sample was received by the laboratory/organization performing the testing: 12/27/2023
The quantity of what the sample constitutes: 2 sets of 4 test bars
A brief description of the sample: #11 HRC xtender 500/510 couplers
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier: 01-330386L
Structure name: SB Koopman
The fabricator/manufacturer/facility name: HRC Fountain Valley

Material Information

Production or Authorization Testing: Production Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Vinton Steel, CMC Steel OK, CMC Steel AZ
Coupler Manufacturer: HRC Fountian Valley CA
Intermediate Assembler or Fabricator:
Rebar Size: #11
Coupler Model: HRC Xtender XT 500/510
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): 73126937 and 73130586
Rebar Heat Number(s): 2212350, 6039401, 4133769
Rebar Size 2 : 11
Coupler Unique ID: TP-17-01

Test Results

Test 1 of 1

DIME Test ID: 2023-11-09-52-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Verified Date: 12/28/2023
Date Tested: 12/19/2023
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Number of Samples 8
SampleMfg. Lot Number(s)SizeArea (sqin)Slip (inch)Peak Load (lbf)Peak Stress (psi)CommentsTested By
11111.560.000414598493579Service SpliceA Auvinen
21111.56015199697433Service SpliceA Auvinen
31111.56014838595119Service SpliceA Auvinen
41111.56015162497195Service SpliceA Auvinen
12111.56-0.013015183297328Service SpliceA Auvinen
22111.56015199397431Service SpliceA Auvinen
32111.56015161497189Service SpliceA Auvinen
42111.56014819694997Service SpliceA Auvinen
Temperature 72 f
UTM 400KIP
Halo ID Small