Project ID: 7285 DEA: 040120T4 EFIS: 0400000027
QA Service Level: 1
DIST-CO-RTE-PM: 04-SF-80-12.6/13.9
Work Description: CONSTRUCT BRIDGE, ROADWAYS, ELECTRICAL, BUILDINGS AND REMOVE BRIDGES
Location Description: THE CITY AND COUNTY OF SAN FRANCISCO FROM THE YERBA BUENA TUNNEL TO 1.3 KM EAST OF THE YERBA BUENA TUNNEL
Contractor Name: CALIFORNIA ENGINEERING CONTRACTORS, INC.
Contractor Address: 20 HAPPY VALLEY ROAD, PLEASANTON, CA 94566
Resident Engineer: Tom Larwin Structure Rep.: Mehran Ardakanian
DIME Sample ID: 2016-05-16-1
TL Number from the TL Form: Unknown
Sample Submitted By Organization: CT D04 - Oakland (YBITS II) 171 Burma Road Field Laboratory
Sample Organization Contact: (510) 286-0510
Type of Sample: Verification
Type of Material: Cementitious
Sample Taken Date: 05/16/2016
Date that the sample was received by the laboratory/organization performing the testing: 05/13/2016
The quantity of what the sample constitutes: 4 Bags
A brief description of the sample: Grout Material
From where was the sample collected: Source
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Quickcrete
DIME Test ID: 2016-05-16-1-1
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 05/20/2016
Date Tested: 05/18/2016
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no data
|
Compressive strength of 1st specimen (psi)
|
6644 psi
|
Compressive strength of 2nd specimen (psi)
|
6592 psi
|
Compressive strength of 3rd specimen (psi)
|
5976 psi
|
Average Compressive strength (to nearest 10 psi)
|
6400 psi
|
DIME Test ID: 2016-05-16-1-2
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 05/20/2016
Date Tested: 05/20/2016
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no data
|
Compressive strength of 1st specimen (psi)
|
7757 psi
|
Compressive strength of 2nd specimen (psi)
|
7525 psi
|
Compressive strength of 3rd specimen (psi)
|
7937 psi
|
Average Compressive strength (to nearest 10 psi)
|
7740 psi
|
DIME Test ID: 2016-05-16-1-3
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 05/24/2016
Date Tested: 05/24/2016
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no data
|
Compressive strength of 1st specimen (psi)
|
9208 psi
|
Compressive strength of 2nd specimen (psi)
|
9501 psi
|
Compressive strength of 3rd specimen (psi)
|
9830 psi
|
Average Compressive strength (to nearest 10 psi)
|
9510 psi
|
DIME Test ID: 2016-05-16-1-4
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 06/14/2016
Date Tested: 06/14/2016
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no data
|
Compressive strength of 1st specimen (psi)
|
9434 psi
|
Compressive strength of 2nd specimen (psi)
|
11000 psi
|
Compressive strength of 3rd specimen (psi)
|
11020 psi
|
Average Compressive strength (to nearest 10 psi)
|
10480 psi
|